| 2007-10-05 14:17:59 | |
| | |
| | |
| | NONCOMPLIANT |
| | |
| | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE |
| | COMPLIANCE AND RESUBMIT FOR REVIEW |
| | |
| | THESE COMMENTS ARE FROM THE PREVIOUS REVIEW, * |
| | INDICATES FURTHER COMMENT FOR CLARITY. |
| | |
| | 4} PROVIDE LOAD CALCULATIONS PER ARTICLE 220 PART III, |
| | STANDARD OR PART IV OPTIONAL, INDICATE METHOD USED, FOR |
| | THE RESIDENCE SERVICE, AND THE EXISTING LOAD ON THE |
| | EQUIPMENT THATS TO FEED THE NEW SERVICE.* THE EXISTING |
| | LOAD CALCULATION AND RATING ARE NEEDED TO INSURE THE |
| | ADDED LOAD WILL NOT EXCEED THE SERVICE RATING OF THE |
| | GEAR. 230.79 NEC. |
| | |
| | 5} PER 250.122 AN EQUIPMENT GROUNDING CONDUCTOR IS |
| | REQUIRED FROM THE FIRST MEANS OF DISCONNECT TO THE |
| | GUTTER, AND PANELS.* REQUIRED ON THE RISER DIAGRAM. |
| | 215.5 NEC, 106.3.5.4 FBC AS AMENDED. |
| | |
| | 7} INCLUDE BRANCH CIRCUIT WIRE SIZES ON PANEL SCHEDULES |
| | * THIS IS REQUIRED TO REVIEW FOR COMPLIANCE WITH 310.16 |
| | AND240.4. NOTE #7 OF THE ELECTRICAL RESPONSES |
| | INDICATES ALL WIRE IS #12THERE ARE SEVERAL CIRCUIT |
| | BREAKERS LISTED OVER 20 AMPS. |
| | |
| | 10} 210.52(B)(1) DINING ROOM CIRCUITS, VIOLATION, |
| | CIRCUIT 27B.* 210.52(B)(2) NO OTHER OUTLETS THE TWO OR |
| | MORE SMALL-APPLIANCE BRANCH CIRCUITS SPECIFIED IN |
| | 210.52(B)(1) SHALL HAVE NO OTHER OUTLETS. SEE THE |
| | TERRACE IS LISTED ON THIS CIRCUIT. |
| | |
| | 11} SMOKE ALARMS MUST BE INSTALLED TO COMPLY WITH |
| | R313.1 RESIDENTIAL FLORIDA BUILDING CODE. LOCATE ON THE |
| | PLAN. |
| | |
| | 12} THE 2005 NEC WAS ADOPTED BY THE FLORIDA LEGISLATURE |
| | EFFECTIVE 8 DECEMBER 2006. PLEASE INDICATE SAME IN THE |
| | ELECTRICAL NOTES. REMOVE ALL REFERENCES OF NEW YORK |
| | CITY LICENSED ELECTRICIANS, BUREAU OF ELECTRICAL |
| | CONTROL AND OTHER REFERENCES NOT PERTINENT TO THIS |
| | APPLICATION, FROM THE ELECTRICAL SPECIFICATIONS. * |
| | COULD NOT FIND REFERENCE TO THE 2005 NEC. |
| | |
| | PLEASE REMOVE OLD SHEETS, INSERT NEW ONES, SUBMIT OLD |
| | SHEETS TO EXPEDITE REVIEW AND SUBMIT WRITTEN RESPONSE |
| | TO THE COMMENTS MADE IN THIS REVIEW. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561/805-6718 |