2007-10-04 18:59:11PROJECT: 1801 SOUTH FLAGLER DRIVE, SUITE
 1903/#07070044
  
 PROJECT DETAILS: INTERIOR DEMOLITION/ALTERATION
  
 CODE REVIEW: 2004 FLORIDA BUILDING CODE/EXISTING
 BUILDING CODE WITH 2006 REVISIONS.
  
 STATUS: DENIED
  
  
 COMMENTS:
  
 (X) = COMPLIED
  
  
 1) PRIOR TO RE-SUBMITTING THE REVIEWED PLANS, PLEASE
 MAKE CERTAIN TO REVIEW AND ADDRESS EACH COMMENT AS
 NOTED BELOW AND MAKE ALL CORRECTIONS WHERE APPLICABLE.
 FAILURE TO DO SO WILL IMPEDE THE EXPEDITING OF THE
 PERMIT ISSUANCE.
  
 2)NEED TO FILE A NOTICE OF COMMENCEMENT, PER F. S.
 713.13 .
  
 (X) 3)301.5 . A DESIGN PROFESSIONAL OR AN OWNER MUST
 ELECT ONE OR A COMBINATION OF LEVELS OF ALTERATION
 PURSUANT TO SECTION
 303,304 & 305 OF THIS CODE.
  
 (X) 4) AS PER THE FBC 106.3.5, PLEASE PROVIDE THE
 FOLLOWING DATA:
  
 A) BUILDING CONSTRUCTION TYPE
 B) SPRINKLERED OR NON-SPRINKLERED.
  
 (X) 5)PLEASE CONTACT ALEX ORTEGA AT 561.355.3023 EXT.
 1148, AS PER THE FOLLOWING:
  
 105.9 ASBESTOS.
  
 THE ENFORCING AGENCY SHALL REQUIRE EACH BUILDING PERMIT
 FOR THE DEMOLITION OR RENOVATION OF AN EXISTING
 STRUCTURE TO CONTAIN AN ASBESTOS NOTIFICATION STATEMENT
 WHICH INDICATES THE OWNER'S OR OPERATOR'S
 RESPONSIBILITY TO COMPLY WITH THE PROVISIONS OF SECTION
 469.003, FLORIDA STATUTES, AND TO NOTIFY THE DEPARTMENT
 OF ENVIRONMENTAL PROTECTION OF HIS OR HER INTENTIONS TO
 REMOVE ASBESTOS, WHEN APPLICABLE, IN ACCORDANCE WITH
 STATE AND FEDERAL LAW.
  
 6) PLEASE PROVIDE DEMOLITION PLAN.
  
 (X) 7) PLEASE PROVIDE A DOOR SCHEDULE.
  
 (X) 8) INDICATE WALL TYPES AND CLARIFY TYPICAL INTERIOR
 PARTITION DETAIL. THE DETAIL INDICATES A 1/2 PLYWOOD
 SUB-FLOOR OVER LIGHT WEIGHT.
  
 (X) 9) PLEASE INDICATE FINISHED FLOOR COVERINGS.
  
 (X) 10) PLEASE PROVIDE DETAILS FOR FLOOR/CEILING/WALL
 PENETRATION FIRE PROTECTION.
  
 11) SUBMIT PRODUCT SPECIFICATIONS FOR TRANSLUCENT
 GLAZING.
  
 (X) 12) PLEASE INDICATE KITCHEN CLEARANCES AND COUNTER
 HEIGHTS.
  
 (X)13) PLEASE PROVIDE DETAILS FOR FLOATING GYPSUM BOARD
 CEILING.
  
 14) SUBMIT PRODUCT SPECIFICATIONS FOR SANDSTONE
 PANELS/SHOW EXTERIOR WALL SECTION/MECHANICAL
 ATTACHMENT/FASTENER TYPES/GAGE OF S.S.ANGLES.
  
 15) PLEASE INDICATE CEILING HEIGHTS AND INDICATE IF ALL
 EXISTING FLOORS ARE BUILT-UP.
  
 16) PLEASE SHOW DETAIL OF ENTRY DOOR THRESHOLD AND HOW
 IT WILL COMPLY WITH THE FAIR HOUSING ACT.
  
 17) THE SUBFLOOR IS SHOWN AS PLYWOOD. THE FOLLOWING
 SHALL APPLY:
  
 717.5 COMBUSTIBLES IN CONCEALED SPACES IN TYPE I OR II
 CONSTRUCTION.
 COMBUSTIBLES SHALL NOT BE PERMITTED IN CONCEALED SPACES
 OF BUILDINGS OF TYPE I OR II CONSTRUCTION.
 EXCEPTIONS:
 1. COMBUSTIBLE MATERIALS IN ACCORDANCE WITH SECTION
 603.
 2. COMBUSTIBLE MATERIALS COMPLYING WITH SECTION 602 OF
 THE FLORIDA BUILDING CODE, MECHANICAL.
 3. CLASS A INTERIOR FINISH MATERIALS.
 4. COMBUSTIBLE PIPING WITHIN PARTITIONS OR ENCLOSED
 SHAFTS INSTALLED IN ACCORDANCE WITH THE PROVISIONS OF
 THIS CODE. COMBUSTIBLE PIPING SHALL BE PERMITTED WITHIN
 CONCEALED CEILING SPACES WHERE INSTALLED IN ACCORDANCE
 WITH THE FLORIDA BUILDING CODE, MECHANICAL AND THE
 FLORIDA BUILDING CODE, PLUMBING.
  
  
  
 PLAN REVIEW: KEN CONRAD
 PHONE: 561.805.6666
 E-MAIL: [email protected]