Plan Review Notes
Plan Review Notes For Permit 07070044
Permit Number 07070044
Review Stop P
Sequence Number 1
Notes
Date Text
2007-07-26 07:20:46DENIED;
 1. ADD NOTE TO PLAN; ICE MACHINE DISCHARGE THROUGH AN
 AIR GAP FITTING.
 2. PLUMBING FLOOR PLAN SHOWS TWO WATER HEATERS WATER
 RISER DIAGRAM SHOWS ONLY ONE. PLEASE EXPLAIN.
 3.SHOW DEMO PLAN. ITS NOT CLEAR WHAT PLUMBING IS BEING
 ALTERED.
 4. SUPPLY CUT SHEET ON HEAT PUMP.
 PLUMBING PLAN REVIEW BY;