| 2007-07-20 15:22:12 | --------------DENIED---------------- |
| | |
| | FBC 2004 CODE FAMILY W/ 2005 AND 2006 REVISIONS |
| | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| | |
| | 1. NO EQUIPMENT SCCHEDULE OR ENERGY CALCULATIONS WERE |
| | PROVIDED. FBC 106.3.5.1.4 |
| | |
| | 2. PG M-1 SHOWS CHILLED WATER BEING SUPPLIED TO FAN |
| | COIL UNITS. THIS BUILDING DOES NOT HAVE A CHILLED WATER |
| | SYSTEM. PG M-2 SHOWS A DIAGRAM FOR PIPING ON A |
| | WATER-COOLED HEAT PUMP. PLEASE COORDINATE DRAWINGS. |
| | |
| | 3. AC NOTE #15. HOW IS CONDENSATE TO BE PIPED TO GRADE |
| | AT EXTERIOR OF THE BUILDING FROM THE 19TH FLOOR? |
| | |
| | 4. NOTE ON M-1 SAYS "REFER TO DWG M103 FOR PIPING |
| | DIAGRAM." NO DRAWING M103 COULD BE FOUND IN PLANS. |
| | |
| | 5. PG M-1 SHOWS TOILET EXHAUST DUCTS ATTACHING TO |
| | (EXISTING?) RISER. DUCT PENETRATIONS OF SHAFTS SHALL BE |
| | PROTECTED BY FIRE AND SMOKE DAMPERS PER FBC,M |
| | 607.5.5.1. ALSO, PLAN SHOWS EXISTING EXHAUST DUCT TO BE |
| | CAPPED AT SHAFT. THIS BECOMES AN UNPROTECTED OPENING. |
| | THE DUCT PENETRATION SHOULD BE COMPLETELY REMOVED WITH |
| | THE SHAFT REPAIRED, OR A FIRE/SMOKE DAMPER IS |
| | REQUIRED. |
| | |
| | 6. EXHAUST DUCTS UNDER POSITIVE PRESSURE SHALL NOT BE |
| | LOCATED IN A PLENUM PER FBC,M 601.3. ALL 3 TX FANS AND |
| | KITCHEN HOOD SHOW EXHAUST DUCT UNDER POSITIVE PRESSURE |
| | IN THE PLENUM CEILING. |
| | |
| | 7. PG M-1 NOTE ON FLOOR PLAN CALLS FOR NEOPRENE |
| | VIBRATION ISOLATORS IN THE PLENUM.MATERIALS EXPOSED |
| | WITHIN PLENUMS SHALL BE NONCOMBUSTIBLE OR SHALL HAVE A |
| | FLAME SPREAD INDEX OF NOT MORE THAN 25 AND A |
| | SMOKE-DEVELOPED INDEX OF NOT MORE THAN 50 WHEN TESTED |
| | IN ACCORDANCE WITH ASTM E 84. FBC,M 602.2.1 |
| | |
| | 8. PLANS SHOW FCU'S ABOVE HARD CEILINGS THROUGHOUT THE |
| | SPACE. ACCESS FOR INSPECTION, SERVICE, REPAIR OR |
| | REPLACEMENT SHALL BE PROVIDED PER FBC,M 306.1 AND |
| | 306.3. |
| | |
| | 9. EACH HYDRONIC HEAT PUMP SHALL HAVE A TWO-POSITION |
| | AUTOMATIC VALVE INTERLOCKED TO SHUT OFF WATER FLOW WHEN |
| | THE COMPRESSOR IS OFF. FBC 13-411.1.ABC.1.4 |
| | |
| | 10. PLEASE PROVIDE PRODUCT APPROVAL FOR OUTDOOR LOUVER |
| | SHOWN AT OFFICE/GUEST ROOM. ALSO, PROVIDE SUBMITTAL FOR |
| | KITCHEN HOOD. FBC 106.1.1. |
| | |
| | 11. NOTE ON FLOOR PLANS THAT A PORTION OF THE WORK TO |
| | BE DONE TO THE PIPING SYSTEM IS TO TAKE PLACEON THE |
| | 18TH FLOOR. THE 18TH FLOOR IS OUTSIDE THE BOUNDARIES OF |
| | THE ADDRESS ON THIS PERMIT APPLICATION. IF ANY WORK IS |
| | TO BE DONE OUTSIDE OF THIS SPACE, PLEASE COORDINATE |
| | WITH ANY OTHER PROPERTY OWNER WHO'S SPACE MAY BE |
| | AFFECTED AS WELL AS BUILDING MANAGEMENT. ADDITIONAL |
| | PERMITS WILL BE REQUIRED FOR ANY WORK TO BE DONE |
| | OUTSIDE THIS SPACE. |
| | |