Plan Review Notes
Plan Review Notes For Permit 07070044
Permit Number 07070044
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2007-07-27 15:04:35***DENIED***
  
 1) LIFE SAFETY TO COMPLY WITH NFPA 101, 2003 EDITION.
 PLEASE ADD ADOPTED EDITION TO GENERAL NOTES.
  
 2) WILL THIS WORK IMPACT ANY EXISTING FIRE PROTECTION
 EQUIPMENT?
  
 3) PLEASE INDICATE MINIMUM FINISH CLASSIFICATION FOR
 WALLS AND CEILING.
  
 4) PLEASE SHOW LOCATION OF REQUIRED SMOKE ALARMS THAT
 ARE REQUIRED TO BE HARD WIRED TO HOUSE ELECTRIC.
 ACTIVATION OF ONE (1) ALARM SHALL CAUSE ALL ALARMS IN
 UNIT TO ACTIVATE.
  
 5) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY
 WITH NFPA 241.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756