Plan Review Notes
Plan Review Notes For Permit 07070044
Permit Number 07070044
Review Stop E
Sequence Number 1
Notes
Date Text
2007-07-11 07:57:36 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW
  
 PER 2704.1, 2004 FBC, METAL FRAMING MEMBERS SHALL BE
 BONDED TO THE EQUIPMENT GROUNDING CONDUCTOR FOR THE
 CIRCUIT THAT MAY ENERGIZE THE FRAMING. PLEASE SEE
 ARTICLE.PUT A COMMENT REGARDING THIS IN THE ELECTRICAL
 SPECIFICATION.
  
 1} THE RISER IS NOT CLEAR AS TO THE MAINS, DISCONNECTS
 OR METER LOCATIONS. INDICATE THE EXISTING LOCATION AS
 WELL AS THE INTENDED LOCATION OF THE NEW METER AND MAIN
 DISCONNECT SHOWN ON THE RISER. (WHAT FLOOR, ELECTRICAL
 ROOM ETC.)
  
 2} INDICATE THE FEEDER CONDUCTOR TYPE ( IG: THHW,
 COPPER) AND CONDUIT TYPE FOR THE NEW FEEDER.
  
 3} SUBMIT THE SPECIFICATIONS (VOLTAGE, AMPERAGE, SYSTEM
 PHASE TYPE) OF THE EQUIPMENT THE PROPOSED FEED IS
 ORIGINATING FROM.
  
 4} PROVIDE LOAD CALCULATIONS PER ARTICLE 220 PART III,
 STANDARD OR PART IV OPTIONAL, INDICATE METHOD USED, FOR
 THE RESIDENCE SERVICE, AND THE EXISTING LOAD ON THE
 EQUIPMENT THATS TO FEED THE NEW SERVICE.
  
 5} PER 250.122 AN EQUIPMENT GROUNDING CONDUCTOR IS
 REQUIRED FROM THE FIRST MEANS OF DISCONNECT TO THE
 GUTTER, AND PANELS.
  
 6} INDICATE THE GUTTER SIZE, SEE ARTICLE 376.22.
  
 7} INCLUDE BRANCH CIRCUIT WIRE SIZES ON PANEL
 SCHEDULES.
  
 8} CIRCUIT #21B DOES NOT COMPLY WITH 210.11(C)(3) BATH
 CIRCUIT, 20 AMP CIRCUIT.
  
 9} 210.11(C)(1) KITCHEN 20 AMP SMALL APPLIANCE
 CIRCUITS.REQUIRED . SEE ARTICLE.
  
 10} 210.52(B)(1) DINING ROOM CIRCUITS, VIOLATION,
 CIRCUIT 27B.
  
 11} SMOKE ALARMS MUST BE INSTALLED TO COMPLY WITH
 R313.1 RESIDENTIAL FLORIDA BUILDING CODE. LOCATE ON THE
 PLAN.
  
 12} THE 2005 NEC WAS ADOPTED BY THE FLORIDA LEGISLATURE
 EFFECTIVE 8 DECEMBER 2006. PLEASE INDICATE SAME IN THE
 ELECTRICAL NOTES. REMOVE ALL REFERENCES OF NEW YORK
 CITY LICENSED ELECTRICIANS, BUREAU OF ELECTRICAL
 CONTROL AND OTHER REFERENCES NOT PERTINENT TO THIS
 APPLICATION, FROM THE ELECTRICAL SPECIFICATIONS.
  
 13} THERE ARE FLOOR BOXES SHOWN ON THE PLAN. PROVIDE A
 DETAIL OF THE FLOOR STRUCTURE COMPONENTS AND A DETAIL ,
 INCLUDING DEPTHS OF CUTS, CONDUIT RUNS AND BOX
 SETTINGS. AN ENGINEER WILL NEED TO PERFOM TESTING TO
 VERIFY THE STRUCTURAL INTEGRITY OF THE FLOOR WILL NOT
 BE IN ANY WAY DIMINISHED BY THIS INSTALLATION. A LETTER
 FROM THE CONDOMINIUM MANAGEMENT ACKNOWLEDGING AWARENESS
 AND THEIR APPROVAL OF THIS INSTALLATION IS ALSO
 REQUIRED.
  
 PLEASE REMOVE OLD SHEETS, INSERT NEW
 ONES, SUBMIT OLD SHEETS TO EXPEDITE
 REVIEW AND SUBMIT WRITTEN RESPONSE TO
 THE COMMENTS MADE IN THIS REVIEW.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  
  