| 2007-07-11 07:57:36 | |
| | |
| | NONCOMPLIANT |
| | |
| | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE |
| | COMPLIANCE AND RESUBMIT FOR REVIEW |
| | |
| | PER 2704.1, 2004 FBC, METAL FRAMING MEMBERS SHALL BE |
| | BONDED TO THE EQUIPMENT GROUNDING CONDUCTOR FOR THE |
| | CIRCUIT THAT MAY ENERGIZE THE FRAMING. PLEASE SEE |
| | ARTICLE.PUT A COMMENT REGARDING THIS IN THE ELECTRICAL |
| | SPECIFICATION. |
| | |
| | 1} THE RISER IS NOT CLEAR AS TO THE MAINS, DISCONNECTS |
| | OR METER LOCATIONS. INDICATE THE EXISTING LOCATION AS |
| | WELL AS THE INTENDED LOCATION OF THE NEW METER AND MAIN |
| | DISCONNECT SHOWN ON THE RISER. (WHAT FLOOR, ELECTRICAL |
| | ROOM ETC.) |
| | |
| | 2} INDICATE THE FEEDER CONDUCTOR TYPE ( IG: THHW, |
| | COPPER) AND CONDUIT TYPE FOR THE NEW FEEDER. |
| | |
| | 3} SUBMIT THE SPECIFICATIONS (VOLTAGE, AMPERAGE, SYSTEM |
| | PHASE TYPE) OF THE EQUIPMENT THE PROPOSED FEED IS |
| | ORIGINATING FROM. |
| | |
| | 4} PROVIDE LOAD CALCULATIONS PER ARTICLE 220 PART III, |
| | STANDARD OR PART IV OPTIONAL, INDICATE METHOD USED, FOR |
| | THE RESIDENCE SERVICE, AND THE EXISTING LOAD ON THE |
| | EQUIPMENT THATS TO FEED THE NEW SERVICE. |
| | |
| | 5} PER 250.122 AN EQUIPMENT GROUNDING CONDUCTOR IS |
| | REQUIRED FROM THE FIRST MEANS OF DISCONNECT TO THE |
| | GUTTER, AND PANELS. |
| | |
| | 6} INDICATE THE GUTTER SIZE, SEE ARTICLE 376.22. |
| | |
| | 7} INCLUDE BRANCH CIRCUIT WIRE SIZES ON PANEL |
| | SCHEDULES. |
| | |
| | 8} CIRCUIT #21B DOES NOT COMPLY WITH 210.11(C)(3) BATH |
| | CIRCUIT, 20 AMP CIRCUIT. |
| | |
| | 9} 210.11(C)(1) KITCHEN 20 AMP SMALL APPLIANCE |
| | CIRCUITS.REQUIRED . SEE ARTICLE. |
| | |
| | 10} 210.52(B)(1) DINING ROOM CIRCUITS, VIOLATION, |
| | CIRCUIT 27B. |
| | |
| | 11} SMOKE ALARMS MUST BE INSTALLED TO COMPLY WITH |
| | R313.1 RESIDENTIAL FLORIDA BUILDING CODE. LOCATE ON THE |
| | PLAN. |
| | |
| | 12} THE 2005 NEC WAS ADOPTED BY THE FLORIDA LEGISLATURE |
| | EFFECTIVE 8 DECEMBER 2006. PLEASE INDICATE SAME IN THE |
| | ELECTRICAL NOTES. REMOVE ALL REFERENCES OF NEW YORK |
| | CITY LICENSED ELECTRICIANS, BUREAU OF ELECTRICAL |
| | CONTROL AND OTHER REFERENCES NOT PERTINENT TO THIS |
| | APPLICATION, FROM THE ELECTRICAL SPECIFICATIONS. |
| | |
| | 13} THERE ARE FLOOR BOXES SHOWN ON THE PLAN. PROVIDE A |
| | DETAIL OF THE FLOOR STRUCTURE COMPONENTS AND A DETAIL , |
| | INCLUDING DEPTHS OF CUTS, CONDUIT RUNS AND BOX |
| | SETTINGS. AN ENGINEER WILL NEED TO PERFOM TESTING TO |
| | VERIFY THE STRUCTURAL INTEGRITY OF THE FLOOR WILL NOT |
| | BE IN ANY WAY DIMINISHED BY THIS INSTALLATION. A LETTER |
| | FROM THE CONDOMINIUM MANAGEMENT ACKNOWLEDGING AWARENESS |
| | AND THEIR APPROVAL OF THIS INSTALLATION IS ALSO |
| | REQUIRED. |
| | |
| | PLEASE REMOVE OLD SHEETS, INSERT NEW |
| | ONES, SUBMIT OLD SHEETS TO EXPEDITE |
| | REVIEW AND SUBMIT WRITTEN RESPONSE TO |
| | THE COMMENTS MADE IN THIS REVIEW. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561/805-6718 |
| | |
| | |