2008-11-12 16:11:43PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 REVISION TO MECHANICAL PLANS.
 *** DENIED ***
  
 1) THE FOLLOWING RETURN AIR DUCTS APPEAR TO BE UNDER
 SIZED. 8" RETURN FLEX TO MASTER BEDROOM (AHU #2), 10"
 RETURN FLEX TO THE LOFT (AHU #3), AND THE 7"X24" CHASE
 FOR AHU #1.
  
 2) SHOW THE SIZE OF THE DUCT (RIGID FIBROUS GLASS) FROM
 AHU #1 TO THE 7"X24" CHASE, PER 2004 FBC/R M1601.1.
  
 3) PLEASE SUBMIT MANUAL D CALCULATIONS FOR RESIDENTIAL
 DUCT DESIGN (3 SYSTEMS), PER 2004 FBC/R M1601.1 AND FBC
 13-610.1.ABC.1. SEE ATTACHED COPY OF MANUAL D
 RECOMMENDED VELOCITY.
  
 4) PLEASE SUBMIT A BLOWER PERFORMANCE TABLE OR GRAPH
 FOR EACH AHU, PER MANUAL D 5-1.
  
 5) PLEASE SUBMIT THE PRODUCT AND PERFORMANCE DATA
 SHEETS FOR THE FLEXIBLE DUCT BEING USED, PER 2004 FBC/R
 M1601.4.
  
 NOTICE: 2004 FBC/R M1602.4 BALANCED RETURN AIR.
 RESTRICTED RETURN AIR OCCURS IN BUILDINGS WHEN RETURNS
 ARE LOCATED IN CENTRAL ZONES AND CLOSED INTERIOR DOORS
 IMPEDE AIR FLOW TO THE RETURN GRILL OR WHEN CEILING
 SPACES ARE USED AS RETURN PLENUMS AND FIRE WALLS
 RESTRICT AIR MOVEMENT FROM ONE PORTION OF THE RETURN
 PLENUM TO ANOTHER. PROVISIONS SHALL BE MADE IN
 RESIDENTIAL BUILDINGS TO AVOID UNBALANCED AIR FLOWS AND
 PRESSURE DIFFERENTIALS CAUSED BY RESTRICTED RETURN AIR.
 PRESSURE DIFFERENTIALS ACROSS CLOSED DOORS WHERE
 RETURNS ARE CENTRALLY LOCATED SHALL BE LIMITED TO 0.01
 INCH WC (2.5 PASCALS) OR LESS. PRESSURE DIFFERENTIALS
 ACROSS FIRE WALLS IN CEILING SPACE PLENUMS SHALL BE
 LIMITED TO 0.01 INCH WC (2.5 PASCALS) BY PROVIDING AIR
 DUCT PATHWAYS OR AIR TRANSFER PATHWAYS FROM THE HIGH
 PRESSURE ZONE TO THE LOW ZONE.
 BALANCED RETURN AIR MAY ALSO BE ACHIEVED BY.
 (A) TRANSFER DUCTS MAY ACHIEVE THIS BY INCREASING THE
 RETURN TRANSFER ONE AND ONE HALF TIMES THE CROSS
 SECTIONAL AREA (SQUARE INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM OR SPACE IT'S SERVING AND THE DOOR
 HAVING AT LEAST AN UNRESTRICTED 1 INCH UNDERCUT TO
 ACHIEVE PROPER RETURN AIR BALANCE.
 (B) TRANSFER GRILLES SHALL USE 50 SQUARE INCHES (OF
 GRILLE AREA) TO 100 CFM (OF SUPPLY AIR) FOR SIZING
 THROUGH-THE-WALL TRANSFER GRILLES AND USING AN
 UNRESTRICTED 1-INCH UNDERCUTTING OF DOORS TO ACHIEVE
 PROPER RETURN AIR BALANCE
 (C) HABITABLE ROOMS ONLY SHALL BE REQUIRED TO MEET
 THESE REQUIREMENTS FOR PROPER BALANCED RETURN AIR
 EXCLUDING BATHROOMS, CLOSETS, STORAGE ROOMS AND LAUNDRY
 ROOMS, EXCEPT THAT ALL SUPPLY AIR INTO THE MASTER SUITE
 SHALL BE INCLUDED. PER 2004 FBC/R M1602.4 .
  