Plan Review Notes
Plan Review Notes For Permit 07070042
Permit Number 07070042
Review Stop B
Sequence Number 3
Notes
Date Text
2007-10-27 09:03:38 
  
 PASSED
  
 1)RAS 117 CALCULATIONS ARE INCORRECTLY BASED ON A -45
 PSF, ALL NON INSULATED ROOFING ASSEMBLIES THAT ARE -45
 PSF ARE LIMITATION #9 WHICH DO NOT ALLOW FOR ENHANCED
 FASTENING TO BE CALCULATED SEE PAGE 34 OF NOA THE
 ASSEMBLY THAT YOU ARE USING, BASED ON SHEET 6 OF THE
 DRAWING IS ON PAGE 33 OF THE NOA AND HAS A DESIGN
 PRESSURE OF -52.5 WITH THE 6" O/C PATTERN THAT YOU USED
 IN YOUR CALCULATIONS
  
 *****PLEASE SUBMIT NEW CALCULATIONS TO THE INSPECTOR AT
 TIME OF INSPECTION*****
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716