| Plan Review Notes For Permit 07070042 |
| Permit Number |
07070042 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2007-10-27 09:03:38 | | | | | | | PASSED | | | | | | 1)RAS 117 CALCULATIONS ARE INCORRECTLY BASED ON A -45 | | | PSF, ALL NON INSULATED ROOFING ASSEMBLIES THAT ARE -45 | | | PSF ARE LIMITATION #9 WHICH DO NOT ALLOW FOR ENHANCED | | | FASTENING TO BE CALCULATED SEE PAGE 34 OF NOA THE | | | ASSEMBLY THAT YOU ARE USING, BASED ON SHEET 6 OF THE | | | DRAWING IS ON PAGE 33 OF THE NOA AND HAS A DESIGN | | | PRESSURE OF -52.5 WITH THE 6" O/C PATTERN THAT YOU USED | | | IN YOUR CALCULATIONS | | | | | | *****PLEASE SUBMIT NEW CALCULATIONS TO THE INSPECTOR AT | | | TIME OF INSPECTION***** | | | | | | BLDG PLAN REVIEW | | | ADRIAN MORSE | | | 561-805-6716 |
|