2007-09-25 08:52:01PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) AS NOTED IN LAST REVIEW, ENERGY CALCULATIONS NEED TO
 BE SIGNED BY OWNER/AGENT ALSO, PER 2004 FBC
 13-600.3.ABC.2.
  
 2) THE MECHANICAL PLANS PAGES 18 & 19 NEED THE PRINTED
 NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE
 DESIGN, AND CONTRACTOR INFORMATION IF APPLICABLE ON
 THEM, SEE W.P.B. AMEND. 106.1.3.
  
 3) SHOW ON MECHANICAL PLANS THE ATTIC ACCESS FOR AHU
 #2, SEE FBC/R M1305.1.3.2.
  
 4) SHOW ON MECHANICAL PLAN ALL BATHROOM EXHAUST FANS
 AND CFM'S, SEE ELECTRICAL PLAN AND FBC/R R303.3
 EXCEPT.
  