| 2007-09-24 10:50:13 | |
| | |
| | THESE ARE REPEAT COMMENTS FROM 7/10/07 REVIEW. |
| | |
| | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: |
| | |
| | |
| | THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004 |
| | RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, |
| | NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND |
| | NONCOMPLIANT WITH THE FOLLOWING: |
| | |
| | 1} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST |
| | PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC. |
| | IF AN ARCHITECT OR ENGINEER, COMPLY WITH 418 AND 417 |
| | FS, RESPECTIVELY. THIS COMMENT WAS NOT ADDRESSED.. |
| | |
| | 2} PER 110.9 AND 110.10: OBTAIN THE AVAILABLE FAULT |
| | CURRENT AT THE UTILITY AND CALCULATE THE SAME AT THE |
| | EQUIPMENT. INDICATE THE AIC RATING FOR THE EQUIPMENT IS |
| | EQUAL TO OR GREATER THAN THE AVAILABLE FAULT. THE |
| | CALCULATION GIVEN WAS ONLY AT THE TRANSFORMER, NOT AT |
| | THE SERVICE EQUIPMENT, WHICH IS THE INFORMATION THE |
| | CONTRACTOR NEEDS TO PURCHASE THE CORRECT EQUIPMENT. |
| | |
| | 5} PROVIDE LOAD CALCULATIONS PER ARTICLE 220 PART III, |
| | STANDARD OR PART IV OPTIONAL, INDICATE METHOD USED. THE |
| | CENTRAL HEAT, AND POOL HEATER TOOK A DEMAND AND WAS |
| | THEN FIGURED INTO THE TOTAL LOAD AND ANOTHER DEMAND OF |
| | 40% WAS TAKEN. |
| | THE LOAD CALCULATION IS STILL INCORRECT. THE |
| | CALCULATION APPEARS TO BE PARTLY FROM ARTICLE 220.83. |
| | THE 65% DEMAND ON THE AHU'S, SHOULD BE 100%, SEE |
| | 220.83(B). ALSO ONLY THE LARGEST OF THE A/C OR AHU LOAD |
| | SHOULD BE IN THE CALCULATION, AGAIN SEE 220.83(B). THE |
| | 40 PERCENT DEMAND TAKEN ON THAT LOAD IS IS NEVER |
| | ALLOWED. IN THE CASE OF THE AHU'S A DOUBLE DEMAND WAS |
| | TAKEN, 1ST THE 65% THEN 40% OF THAT. |
| | |
| | THIS IS A NEW COMMENT FOR THIS REVIEWDUE TO THE CHANGE |
| | IN THE RISER DIAGRAM |
| | |
| | 1} LOCATE THE GUTTER SHOWN ON THE RISER, AT THE |
| | PHYSICAL LOCATION ON THE PLAN |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |