Plan Review Notes
Plan Review Notes For Permit 07070042
Permit Number 07070042
Review Stop E
Sequence Number 2
Notes
Date Text
2007-09-24 10:50:13 
  
 THESE ARE REPEAT COMMENTS FROM 7/10/07 REVIEW.
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC.
 IF AN ARCHITECT OR ENGINEER, COMPLY WITH 418 AND 417
 FS, RESPECTIVELY. THIS COMMENT WAS NOT ADDRESSED..
  
 2} PER 110.9 AND 110.10: OBTAIN THE AVAILABLE FAULT
 CURRENT AT THE UTILITY AND CALCULATE THE SAME AT THE
 EQUIPMENT. INDICATE THE AIC RATING FOR THE EQUIPMENT IS
 EQUAL TO OR GREATER THAN THE AVAILABLE FAULT. THE
 CALCULATION GIVEN WAS ONLY AT THE TRANSFORMER, NOT AT
 THE SERVICE EQUIPMENT, WHICH IS THE INFORMATION THE
 CONTRACTOR NEEDS TO PURCHASE THE CORRECT EQUIPMENT.
  
 5} PROVIDE LOAD CALCULATIONS PER ARTICLE 220 PART III,
 STANDARD OR PART IV OPTIONAL, INDICATE METHOD USED. THE
 CENTRAL HEAT, AND POOL HEATER TOOK A DEMAND AND WAS
 THEN FIGURED INTO THE TOTAL LOAD AND ANOTHER DEMAND OF
 40% WAS TAKEN.
 THE LOAD CALCULATION IS STILL INCORRECT. THE
 CALCULATION APPEARS TO BE PARTLY FROM ARTICLE 220.83.
 THE 65% DEMAND ON THE AHU'S, SHOULD BE 100%, SEE
 220.83(B). ALSO ONLY THE LARGEST OF THE A/C OR AHU LOAD
 SHOULD BE IN THE CALCULATION, AGAIN SEE 220.83(B). THE
 40 PERCENT DEMAND TAKEN ON THAT LOAD IS IS NEVER
 ALLOWED. IN THE CASE OF THE AHU'S A DOUBLE DEMAND WAS
 TAKEN, 1ST THE 65% THEN 40% OF THAT.
  
 THIS IS A NEW COMMENT FOR THIS REVIEWDUE TO THE CHANGE
 IN THE RISER DIAGRAM
  
 1} LOCATE THE GUTTER SHOWN ON THE RISER, AT THE
 PHYSICAL LOCATION ON THE PLAN
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER