Plan Review Notes
Plan Review Notes For Permit 07070042
Permit Number 07070042
Review Stop M
Sequence Number 1
Notes
Date Text
2007-07-11 09:30:48*** DENIED ***
 1) ENERGY CALCULATIONS NEED TO BE ON FORM 600A-04R,
 PLEASE CORRECT ALSO HAVE OWNER/AGENT SIGN REVISED
 E-CAL'S. SEE 2004 FBC 13-600.3.A AND 13-600.3.ABC.2.
  
 2) MECHANICAL PLANS NEED TO BE SEALED BY JOHN CRESWELL,
 P.E. AS HIS NAME AND INFORMATION IS IN THE TITLE BLOCK,
 SEE FAC 61G15-23.002.
  
 3) NEED A/C EQUIPMENT LISTING ON MECHANICAL PLANS
 SHOWING ALL PERTINENT INFORMATION (EQUIPMENT
 MANUFACTURE, MODEL NUMBERS, SEER, TOTAL AND SENSIBLE
 BTU'S, HEATER KW, ETC.).
  
 4) PLEASE SHOW CFM'S AT ALL SUPPLY AIR GRILLS.
  
 5) PLEASE SIZE THE SUPPLY AIR TRUNK LINE TO THE AIR
 HANDLER IN THE GARAGE.
  
 6) THE SECOND FLOOR NEEDS A RETURN FOR THE LOFT AND
 OPEN AREA, SEE 2004 FBC/R M1604.2.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.