 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC.
 IF AN ARCHITECT OR ENGINEER, COMPLY WITH 418 AND 417
 FS, RESPECTIVELY.
  
 2} PER 110.9 AND 110.10: OBTAIN THE
 AVAILABLE FAULT CURRENT AT THE UTILITY
 AND CALCULATE THE SAME AT THE EQUIPMENT.
 INDICATE THE AIC RATING FOR THE
 EQUIPMENT IS EQUAL TO OR GREATER THAN
 THE AVAILABLE FAULT.
  
 3} 230.31 SIZE AND RATING
 (A) GENERAL SERVICE-LATERAL CONDUCTORS SHALL HAVE
 SUFFICIENT AMPACITY TO CARRY THE CURRENT FOR THE LOAD
 AS CALCULATED IN ACCORDANCE WITH ARTICLE 220 AND SHALL
 HAVE ADEQUATE MECHANICAL STRENGTH. THE LOAD CALCULATION
 @ 244 AMPS, EXCEEDS THE SERVICE SIZE OF 200 AMPS. THE
 SERVICE MUST BE INCREASED.
  
 4} PROVIDE A PANEL SCHEDULE PER 408.4. PLEASE SEE NEW
 VERBAGE FOR 2005 NEC: "THE IDENTIFICATION SHALL INCLUDE
 SUFFICIENT DETAIL TO ALLOW EACH CIRCUIT TO BE
 DISTINGUISHED FROM ALL OTHERS." ALL PANELS.
  
 5} PROVIDE LOAD CALCULATIONS PER ARTICLE 220 PART III,
 STANDARD OR PART IV OPTIONAL, INDICATE METHOD USED. THE
 CENTRAL HEAT, AND POOL HEATER TOOK A DEMAND AND WAS
 THEN FIGURED INTO THE TOTAL LOAD AND ANOTHER DEMAND OF
 40% WAS TAKEN.
  
 6} THE POOL HEATER WAS CALCULATED @ 40%, INDICATE THE
 ARTICLE FROM WHICH THAT DEMAND WAS ALLOWED.
  
 7} PROVIDE A LEGEND FOR THE SYMBOLS USED FOR THE
 ELECTRICAL PLANS.
  
 8} THE CONDENSING UNITS ARE REQUIRED TO HAVE
 DISCONNECTS PER 440.14, THE PLAN INDICATES JUNCTION
 BOXES. PLEASE CLARIFY.
  
 9} THE SPA MUST BE GFCI PROTECTED PER 680.43(A)(3).
 INDICATE SAME ON PLAN.
  
 10} THE WATER HEATER IN THE GARAGE IS SHOWN NEXT TO A
 RECEPTACLE, AND THERE DOES NOT APPEAR TO BE A
 DISCONNECT FOR THAT UNIT. SEE 422.16 REGARDING
 "APPLIANCE IS INTENDED OR IDENTIFIED FOR FLEXIBLE CORD
 CONNECTION".
  