| 2007-07-10 12:27:30 | |
| | |
| | NONCOMPLIANT |
| | |
| | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE |
| | COMPLIANCE AND RESUBMIT FOR REVIEW. |
| | |
| | 1} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST |
| | PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC. |
| | IF AN ARCHITECT OR ENGINEER, COMPLY WITH 418 AND 417 |
| | FS, RESPECTIVELY. |
| | |
| | 2} PER 110.9 AND 110.10: OBTAIN THE |
| | AVAILABLE FAULT CURRENT AT THE UTILITY |
| | AND CALCULATE THE SAME AT THE EQUIPMENT. |
| | INDICATE THE AIC RATING FOR THE |
| | EQUIPMENT IS EQUAL TO OR GREATER THAN |
| | THE AVAILABLE FAULT. |
| | |
| | 3} 230.31 SIZE AND RATING |
| | (A) GENERAL SERVICE-LATERAL CONDUCTORS SHALL HAVE |
| | SUFFICIENT AMPACITY TO CARRY THE CURRENT FOR THE LOAD |
| | AS CALCULATED IN ACCORDANCE WITH ARTICLE 220 AND SHALL |
| | HAVE ADEQUATE MECHANICAL STRENGTH. THE LOAD CALCULATION |
| | @ 244 AMPS, EXCEEDS THE SERVICE SIZE OF 200 AMPS. THE |
| | SERVICE MUST BE INCREASED. |
| | |
| | 4} PROVIDE A PANEL SCHEDULE PER 408.4. PLEASE SEE NEW |
| | VERBAGE FOR 2005 NEC: "THE IDENTIFICATION SHALL INCLUDE |
| | SUFFICIENT DETAIL TO ALLOW EACH CIRCUIT TO BE |
| | DISTINGUISHED FROM ALL OTHERS." ALL PANELS. |
| | |
| | 5} PROVIDE LOAD CALCULATIONS PER ARTICLE 220 PART III, |
| | STANDARD OR PART IV OPTIONAL, INDICATE METHOD USED. THE |
| | CENTRAL HEAT, AND POOL HEATER TOOK A DEMAND AND WAS |
| | THEN FIGURED INTO THE TOTAL LOAD AND ANOTHER DEMAND OF |
| | 40% WAS TAKEN. |
| | |
| | 6} THE POOL HEATER WAS CALCULATED @ 40%, INDICATE THE |
| | ARTICLE FROM WHICH THAT DEMAND WAS ALLOWED. |
| | |
| | 7} PROVIDE A LEGEND FOR THE SYMBOLS USED FOR THE |
| | ELECTRICAL PLANS. |
| | |
| | 8} THE CONDENSING UNITS ARE REQUIRED TO HAVE |
| | DISCONNECTS PER 440.14, THE PLAN INDICATES JUNCTION |
| | BOXES. PLEASE CLARIFY. |
| | |
| | 9} THE SPA MUST BE GFCI PROTECTED PER 680.43(A)(3). |
| | INDICATE SAME ON PLAN. |
| | |
| | 10} THE WATER HEATER IN THE GARAGE IS SHOWN NEXT TO A |
| | RECEPTACLE, AND THERE DOES NOT APPEAR TO BE A |
| | DISCONNECT FOR THAT UNIT. SEE 422.16 REGARDING |
| | "APPLIANCE IS INTENDED OR IDENTIFIED FOR FLEXIBLE CORD |
| | CONNECTION". |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |