| 2007-07-06 09:02:49 | *** PROVISO *** | | | 1) 2004 FBC/M 606.2.2 COMMON SUPPLY, RETURN AIR AND | | | SUPPLY AIR SYSTEMS. | | | WHERE MULTIPLE AIR-HANDLING SYSTEMS SHARE COMMON SUPPLY | | | OR RETURN AIR DUCTS OR PLENUMS WITH A COMBINED DESIGN | | | CAPACITY GREATER THAN 2,000 CFM (0.9 M 3 /S), THE | | | RETURN AIR AND SUPPLY AIR SYSTEM SHALL BE PROVIDED WITH | | | SMOKE DETECTORS IN ACCORDANCE WITH SECTION 606.2.1 . | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|