2007-07-25 14:06:33DENIED;
 1. CHECK VALVE AND FULL OPEN VALVE REQUIRED ON
 DISCHARGE SIDE OF PUMP. FBC-2004 PLUMBING SECTION
 712.2.
 2. SANITARY RISER DIAGRAM PIPE SIZING NOT THE SAME AS
 FLOOR PLAN DISCHARGEPIPE 1 1/2 ON RISER DIAGRAM 2 ON
 FLOOR PLAN.
 3. KITCHEN SINK TO BE HANDICAP ACCESSIBLE. SEE FBC-2004
 CHAPTER 11 SECTIONS 11-4.24.2 MAX. HIGHT OF SINK,
 11-4.24.3 KNEE CLEARANCE, 11-4.24.4 DEPTH UNDER SINK
 (NO CABINET DOORS), 11-4.24.5 CLEAR FLOOR SPACE,
 11-4.24.6 RAP PIPES, AND 11-4.24.7 FAUCET. SHOW DETAIL
 ON PLANS WITH ALL REQUIRED MESSUREMENT. SHOW CLEAR
 FLOOR SPACE ON FLOOR PLAN.