1 |
|
| Notes |
| Date |
Text |
| 2007-07-23 10:27:25 | DENIED; | | | 1. SANITARY RISER DIAGRAM; | | | A) AUTOMATIC CLOTHES WASHERS ARE NOT PERMITED | | | TO DUMP INTO A SANITARY CROSS SEFBC-2004 PLUMBING | | | SECTION 706.3. | | | B) LABLE ALL FIXTURES. | | | C) EXPLAIN SANITARY STUB. | | | D) LAUNDRY TUB NOT SHOWN. | | | 2. WATER RISER; SHOW WATER HAMMER ARRESTORS WHERE | | | REQUIRED AND SPEC OUT SIZE AND MANUFATURE. SEE SECTION | | | 604.9 | | | 3. PLUMBING NOTE # 8 PIPE2 1/2" AND SMALLER MUST PITCH | | | 1/4" PER FOOT. SEE TABLE 704.1. | | | 4. BREAK SINK MUST MEET THE REQUIREMENTS OF FBC-2004 | | | BUILDING CHAPTER 11 ACCESSIBITY CODE SEE SECTIONS; | | | 11-4.24.2 HEIGHT | | | 11-4.24.3 KNEE CLEARANCE UNDER SINK ( NO | | | DOORS) | | | 11-4.24.4 DEPTH OF SINK. ( 6 1/2 DEEP MAX. | | | 11-4.24.5 CLEAR FLOOR SPACE SHOW ON PLANS. | | | 11-4.24.6 RAP EXPOSED PIPES. | | | 11-4.24.7 LEVER OPERATED FAUCETS. | | | PLUMBING PLAN REVIEW BY | | | JOHN LEECH | | | 805-6695 |
|