| Plan Review Notes For Permit 07070033 |
| Permit Number |
07070033 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-07-23 10:43:20 | DENIED; | | | 1. GAS RISER DIAGRAM IS NOT SIZED THE SAME AS GAS LOAD | | | CALCULATIONS. SIZING ON DIAGRAM IS TOO SMALL SEE SIZING | | | TABLE 402.4(2). | | | 2. SHOW COMPLIANCE FOR COMBUSTION AIR AS | | | PER 2001 FBC(M) CHAPTER 7. ( DRYERS) | | | | | | 3. PROVIDE MANUFACTURE CUT SHEETS FOR WATER HEATERS. | | | GAS PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|