| 2007-07-12 19:08:35 | PROJECT: 1551 NORTH FLAGLER DRIVE |
| | |
| | REVIEW: 2004 FLORIDA BUILDING CODE WITH 2006 REVISIONS |
| | |
| | STATUS: DENIED |
| | |
| | COMMENTS: |
| | |
| | |
| | 1) PLEASE REVISE OCCUPANCY TYPE TO REFLECT BUSINESS |
| | GROUP B AS PER THE FBC, SECTION 304.1. ALSO INDICATE |
| | OCCUPANCY LOAD. |
| | |
| | 2) PLEASE REVISE THE INDICATED CONSTRUCTION TYPE. THIS |
| | BUILDING WAS CONSTRUCTED AS A TYPE 1. |
| | |
| | 3) PLEASE INDICATE THE MECHANICAL ATTACHMENT OF THE |
| | RUNNER CHANNEL TO THE EXISTING STRUCTURE. ALSO PROVIDE |
| | CLARIFICATION OF EXISTING FRAMING MEMBER: WOOD OR STEEL |
| | JOISTS. |
| | |
| | 4) SHOW MECHANICAL ATTACHMENT OF THE METAL FRAMING |
| | DIAGONAL BRACING TO EXISTING STRUCTURE CONNECTION. SEE |
| | DETAIL 1 ON SHEET A3 OF 8. |
| | |
| | 5) PROVIDE SPECIFICATIONS FOR CMU WALL INSULATION. |
| | |
| | 6) PLEASE SHOW FINISHED COUNTERTOP HEIGHTS ON FLOOR |
| | PLAN, SHEET A1 OF 8. |
| | |
| | 7) PLEASE PROVIDE FIRE-STOPPING DETAILS IF APPLICABLE. |
| | |
| | 8) FIRE- BLOCKING SHALL CONFORM TO THE FOLLOWING: |
| | |
| | 717.1 GENERAL. |
| | FIREBLOCKING AND DRAFTSTOPPING SHALL BE INSTALLED IN |
| | COMBUSTIBLE CONCEALED LOCATIONS IN ACCORDANCE WITH THIS |
| | SECTION. FIREBLOCKING SHALL COMPLY WITH SECTION 717.2. |
| | DRAFTSTOPPING IN FLOOR/CEILING SPACES AND ATTIC SPACES |
| | SHALL COMPLY WITH SECTIONS 717.3 AND 717.4, |
| | RESPECTIVELY. THE PERMITTED USE OF COMBUSTIBLE |
| | MATERIALS IN CONCEALED SPACES OF NONCOMBUSTIBLE |
| | BUILDINGS SHALL BE LIMITED TO THE APPLICATIONS |
| | INDICATED IN SECTION 717.5. |
| | |
| | 9) COMBUSTIBLES IN CONCEALED SPACES SHALL COMPLY WITH |
| | THE FOLLOWING: |
| | |
| | 717.5 COMBUSTIBLES IN CONCEALED SPACES IN TYPE I OR II |
| | CONSTRUCTION. |
| | COMBUSTIBLES SHALL NOT BE PERMITTED IN CONCEALED SPACES |
| | OF BUILDINGS OF TYPE I OR II CONSTRUCTION. |
| | EXCEPTIONS: |
| | 1. COMBUSTIBLE MATERIALS IN ACCORDANCE WITH SECTION |
| | 603. |
| | 2. COMBUSTIBLE MATERIALS COMPLYING WITH SECTION 602 OF |
| | THE FLORIDA BUILDING CODE, MECHANICAL. |
| | 3. CLASS A INTERIOR FINISH MATERIALS. |
| | 4. COMBUSTIBLE PIPING WITHIN PARTITIONS OR ENCLOSED |
| | SHAFTS INSTALLED IN ACCORDANCE WITH THE PROVISIONS OF |
| | THIS CODE. COMBUSTIBLE PIPING SHALL BE PERMITTED WITHIN |
| | CONCEALED CEILING SPACES WHERE INSTALLED IN ACCORDANCE |
| | WITH THE FLORIDA BUILDING CODE, MECHANICAL AND THE |
| | FLORIDA BUILDING CODE, PLUMBING. |
| | |
| | 10) FIRE RETARDANT TREATED LUMBER SHALL BE USED AS PER |
| | THE FOLLOWING SECTION: |
| | |
| | 603.1 ALLOWABLE MATERIALS. |
| | COMBUSTIBLE MATERIALS SHALL BE PERMITTED IN BUILDINGS |
| | OF TYPE I OR II CONSTRUCTION IN THE FOLLOWING |
| | APPLICATIONS AND IN ACCORDANCE WITH SECTIONS 603.1.1 |
| | THROUGH 603.1.3: |
| | 1. FIRE-RETARDANT-TREATED WOOD SHALL BE PERMITTED IN: |
| | 1.1. NONBEARING PARTITIONS WHERE THE REQUIRED |
| | FIRE-RESISTANCE RATING IS 2 HOURS OR LESS. |
| | 1.2. NONBEARING EXTERIOR WALLS WHERE NO FIRE RATING IS |
| | REQUIRED. |
| | 1.3. ROOF CONSTRUCTION AS PERMITTED IN TABLE 601, NOTE |
| | C, ITEM 3. |
| | |
| | |