Plan Review Notes
Plan Review Notes For Permit 07070020
Permit Number 07070020
Review Stop B
Sequence Number 4
Notes
Date Text
2007-10-19 15:33:58****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.PLANS ARE TO SHOW CODE COMPLIANCE.THE RESPONSE
 LETTER CAN BE HELPFUL IN EXPLAINING HOW A COMMENT WAS
 ADDRESSED. BUT THE PLANS SHOULD CLEARLY SHOW SCOPE OF
 WORK.
  
 2.THE RESPONSE LETTER GIVES INFORMATION WHICH IS
 DESIGN RELATED.ONLY CODE COMPLIANCE IS ADDRESSED IN
 THE PLAN REVIEW.IT APPEARS THAT YOU ARE CLOSING AN
 EXISTING OPENING AND CREATING A NEW ONE.THIS NEEDS TO
 BE SHOWN ON THE PLAN, USING THE FLOOR PLAN, DETAILS,
 AND DETAIL MARKERS.
  
 3.PROVIDE A DETAIL FOR THE INFILL AND A DETAIL FOR
 THE FRAMING OF THE NEW OPENING.STATING THAT YOU ARE
 INSTALLING 4 STUDS IS NOT SUFFICIENT NOR CODE
 COMPLIANT.
  
 4.ON THE INSTALLATION SCHEDULE, STATE WHICH
 CONNECTION TYPE YOU ARE USING.YOU'VE CIRCLED ALL OF
 THEM ON THE PRODUCT APPROVAL.THE 6" SPACING WHICH YOU
 SPECIFY IS NOT COMPLIANT FOR ALL CONNECTION MOUNTING
 TYPES.THIS SHOULD BE A THROUGH L, SEE SHEETS 13-15.
  
 5.A 2" EDGE DISTANCE REQUIRES A FACTOR OF .5, SEE
 SHEET 14 OF THE PRODUCT APPROVAL.INFORMATIONAL;
 AFFECTS ANCHOR SPACING, CANNOT BE REVIEWED AS
 CONNECTION MOUNTING TYPE HAS NOT BEEN SPECIFIED.
  
 6.SPANS SHOULD EQUAL BLADE LENGTH, SO SHOULD
 CORRELATE WITH THE OPENING HEIGHT.REVISE INSTALLATION
 SCHEDULE.
  
 7.THE FIRST COMMENT LISTS REQUESTED THAT THE PLANS
 SHOW HOW EMERGENCY EGRESS FOR BEDROOMS WILL BE
 ADDRESSED.IT IS NOT CLEAR HOW THIS HAS BEEN
 ADDRESSED, FBC 310, FBC EB505.1.
  
 8.ANOTHER COMMENT LIST HAD REQUESTED THAT THE
 APPLICATION BE REVISED TO REFLECT SCOPE OF WORK (AFTER
 CONTRACTOR STATED THAT ONLY S/H WINDOWS WERE BEING
 INSTALLED).IT STILL STATES "DUAL ACTION AND SINGLE
 HUNG".PLANS ARE TO SHOW WHICH WINDOW TYPE WILL BE
 INSTALLED IN EACH LOCATION.REVISE APPLICATION IF ONLY
 ONE WINDOW TYPE IS BEING INSTALLED.
  