2007-08-20 08:49:37****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.)SHUTTER MOUNTING CONNECTION TYPE SHOULD REFER TO A
 THROUGH L TO CORRELATE WITH THE ANCHOR SCHEDULE ON THE
 PRODUCT APPROVAL.
  
 2.)YOU'VE HIGHLIGHTED A, D, G, H CONNECTION TYPES ON
 THE PRODUCT APPROVAL.A AND D REQUIRE CONCRETE
 SUBSTRATE.I CANNOT READ THE SUBSTRATE; APPEARS TO
 STATE CONCRETE, LOCKING RRD IN THE CENTER BOLD COLUMN.
 PLEASE CLARIFY SUBSTRATE.
  
 3.)YOU'VE HIGHLIGHED THE .78 FACTOR REQUIRED FOR 3"
 EDGE DISTANCE BUT HAVE NOT APPLIED THIS FACTOR TO THE
 HIGHLIGHTED ANCHOR SPACING ON THE SCHEDULE.PLEASE
 CAREFULLY READ THIS SECTION OF THE PRODUCT APPROVAL AND
 REVISE THE INSTALLATION SCHEDULE ACCORDINGLY.
  