| 2007-07-05 15:57:32 | ****CORRECTIONS**** |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC EBFLORIDA BUILDING CODE 2004 |
| | EXISTING BUILDING CODE |
| | FBC*CITY OF WEST PALM BEACH |
| | AMENDMENTS TO THE FBC2004 |
| | |
| | FROM PREVIOUS LIST: |
| | |
| | _XX_4.)FOR THE FLAT DECK, SELECT THE APPROVED |
| | ASSEMBLY YOU ARE USING.ALSO INDICATE WHICH FASTENER |
| | YOU ARE USING IF THE OPTIONS HAVE DIFFERENT PRESSURE |
| | LIMITATIONS. |
| | |
| | 2ND REVIEW - THERE IS A NOTE WHICH STATES "SEE PAGES |
| | 2,3,14,15".PLEASE CHOOSE AN ASSEMBLY.IT APPEARS |
| | THAT YOU MAY BE PROPOSING TO USE THE ASSEMBLY ON PAGES |
| | 14-15, BUT ENHANCED FASTENING IS FOR BASE SHEET RATHER |
| | THAN INSULATION BOARD, AND PAGES 2 AND 3 ARE A LISTING |
| | OF PRODUCTS (NOT ASSEMBLIES).PLEASE MARK AN ASSEMBLY |
| | OR NOTE WHICH PAGE(S) THE ASSEMBLY IS ON, BUT REFER |
| | ONLY TO ONE OR TWO PAGES, ONE ASSEMBLLY ONLY. |
| | |
| | _XX_5.)FOR THE FLAT DECK, SPECIFY THE ENHANCED |
| | FASTENING FOR CORNER AND PERIMETER ZONES. |
| | |
| | 2ND REVIEW - THIS WAS WRITTEN ON TH EAPPLICATION AND ON |
| | THE CORRECTION LIST.THIS IS TO BE A PART OF YOUR |
| | PERMIT PACKAGE.PLEASE PROVIDE THE INFORMATION EITHER |
| | ON LETTERHEAD, A SEPARATE SHEET, OR WRITE IT DIRECTLY |
| | ON THE PRODUCT APPROVAL.TWO SETS OF ALL PERMIT |
| | DOCUMENTS ARE REQUIRED.ALSO, YOUR STATEMENT - "4 " |
| | O.C. PERIMETER4" O.C. " NOT ENTIRELY CLEAR, AND |
| | APPEARS TO BE FASTENING FOR A BASE SHEET, BUT YOU'VE |
| | SELECTED AN ASSEMBLY WITH INSULATION, SO ENHANCED |
| | FASTENING SHOULD STATE NUMBER OF FASTENERS PER BOARD. |
| | SEE RAS117. |
| | |
| | |