| Date |
Text |
| 2007-09-25 10:08:48 | DENIED 2ND TIME |
| | REFERENCE: |
| | ** FBC-2004 WITH 2006 REVISIONS, FUEL GAS. |
| | ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION |
| | REQUIREMENTS. |
| | ** FBC-2004 CHAPTER 1, THE CITY OF |
| | WEST PALM BEACH AMENDMENTS. |
| | ** FLORIDA ADMINISTRATIVE CODE. |
| | ** FLORIDA STATUTES. |
| | |
| | ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ARE STILL |
| | IN NEED OF ADDRESSING ALONG WITH SOME NEW COMMENTS, |
| | SOME BASED ON PLANS NOW SUBMITTED, NEW DOCUMENTS BEING |
| | REVIEWED FOR THE FIRST TIME AND SOME NEW COMMENTS NOT |
| | MADE ON PREVIOUS REVIEWS. |
| | |
| | ** PLEASE SEE THE NOTES BELOW ARE TAKEN DIRECTLY FROM |
| | PREVIOUS REVIEW WITH A NO, OK OR A NO/OK. |
| | THESE WILL BE FOR THE EXACT NUMERICAL NOTATION OF THE |
| | PREVIOUS REVIEW NOTES. |
| | |
| | A NO IS IF THE COMMENT WAS NOT FULLY ADDRESSED AND/OR |
| | FURTHER EXPLANATION OR CHANGES IN PLANS OR DOCUMENTS |
| | ARE STILL NEEDED. THIS REVIEWER WILL TRY TO BETTER |
| | EXPLAIN NOTE ABOVE PREVIOUS REVIEW COMMENT. |
| | |
| | AN OK WILL BE LABELED AS SUCH ON THE SAME NUMERICAL |
| | COMMENT AND WILL HAVE OLD NOTE REMOVED FROM COMMENTS. |
| | |
| | A NO/OK MEANS PART OF THE COMMENT MAY HAVE BEEN |
| | ADDRESSED, HOWEVER NOT ALL OF THE PREVIOUS REVIEW |
| | COMMENT MAY HAVE BEEN FULLY ADDRESSED. |
| | |
| | ** PLEASE SEE ANY NEW NOTES WILL BE ADDED TO THE END OF |
| | THE PREVIOUS REVIEW COMMENTS AND NOTED AS SUCH. |
| | |
| | 1. **NO** SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE. |
| | NOTE: THE RESUBMITTED DRAWING IS NOT AN ISOMETRIC AND |
| | DOES NOT SHOW ALL CUT SECTIONSAND CORRESPONDING |
| | LENGTHS TO THE PROPOSED GENERATOR. THE ONLY PIPING |
| | INDICATED IS THE UNDERGROUND PE PIPE, THERE ARE NO |
| | INDICATIONS OF THE ABOVE GROUND PIPING, 1ST AND 2ND |
| | STAGE REGULATORS, SHUT OFF VALVES AND SEDIMENT TRAPS. |
| | PER FBC-2004 CHAPTER 1, SECTION 106.1.1 INFORMATION ON |
| | CONSTRUCTION |
| | DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL |
| | BE OF SUFFICIENT CLARITY TO INDICATE THE |
| | LOCATION, NATURE AND EXTENT OF THE WORK |
| | PROPOSED AND SHOW IN DETAIL THAT IT WILL |
| | CONFORM TO THE PROVISIONS OF THIS CODE |
| | AND RELAVENT LAWS, ORDINANCES, RULES AND REGULATIONS, |
| | AS DETERMINED BY THE |
| | BUILDING OFFICIAL. |
| | |
| | 2. **NO/OK** SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE BEING USED. |
| | NOTE: REFERENCE COMMENT 1, WHERE ONLY THE UNDERGROUND |
| | PIPING IS BEING INDICATED. |
| | |
| | 3. **OK** |
| | |
| | 4. **OK** |
| | |
| | 5. **OK** |
| | |
| | 6. **OK** |
| | |
| | 7. **NO** INDICATE THE DELIVERY PRESSURE ON THE |
| | RESUBMITTAL, IF ITS LP GAS INDICATE 10 PSI. |
| | |
| | 8. **OK** |
| | |
| | 9. **NO** SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2. |
| | NOTE: NEED MANUFACTURER SHEETS ON THE PROPOSED |
| | GENERATOR VERIFYING THE BTU LOAD AND MANUFACTURER |
| | SHEETS OF THE 2ND STAGE REGULATOR TO THE PROPOSED |
| | GENERATOR INDICATING THE MAKE, MODEL NUMBER, LOAD |
| | CAPACITY AND A LISTING FROM A NATIONALLY RECOGNIZED |
| | TESTING LABORATORY. |
| | |
| | 10. **OK** |
| | |
| | 11. **OK** |
| | |
| | 12. **OK** |
| | |
| | END OF COMMENTS: |
| | |
| | REVIEW BY MIKE PERSON |
| | PLUMBING PLANS EXAMINER |
| | (561) 805-6730 |
| | FAX (561) 805-6731 |
| | E-MAIL: [email protected] |
| | |