| 2007-09-04 19:02:42 | *** PROVISO/REVISION NEEDED** |
| | |
| | ** PLEASE SEE SOME EXACT SAME COMMENTS FROM PREVIOUS |
| | REVIEW ALONG WITH NEW COMMENT(S) AS RISER DIAGRAM HAS |
| | CHANGED. |
| | |
| | 1) NOTE: PLEASE SEE PREVIOUS NOTE #12 WHICH |
| | SPECIFICALLY MENTIONED THE LIVING ROOM RECEPTACLES ARE |
| | NOT PERMITTED TO BE ON THE DINING ROOM RECEPTACLE |
| | CIRCUIT. PLANS STILL SHOW BOTH ON THE SAME CIRCUIT?? |
| | PLEASE SEE THIS SAME PREVIOUS NOTE ALSO GAVE THE |
| | INFORMATION AS ONE OR MORE OF THE SMALL APPLIANCE |
| | CIRCUITS ARE REQUIRED TO BE FIGURED AT 1500VA MINIMUM. |
| | PLEASE SEE THE LOAD CALCULATIONS ONLY INDICATE 2 AT |
| | 1500VA. |
| | |
| | 2) NOTE: PLEASE SEE THE RISER HAS NOW BEEN REVISED |
| | REMOVING THE MAIN DISCONNECT WHICH WAS PREVIOUSLY SHOWN |
| | AND IS NOW SHOWING AN EXISTING *MAIN CIRCUIT BREAKER* |
| | PANEL INSIDE THE GARAGE.THE RISER STILLS SHOWS AN |
| | *EQUIPMENT GROUNDING CONDUCTOR* BEFORE THE MAIN NOW |
| | THAT THE MAIN HAS MOVED INSIDE WHICH IS NOT PERMITTED. |
| | THIS PARALLELS THE NEUTRAL AND CREATES OBJECTIONABLE |
| | CURRENTS. |
| | 250.24B AND 250.6. |
| | ** PER HOMEOWNER, THERE IS A METER/MAIN COMBINATION |
| | PANEL AT THE DWELLING WHICH EXISTS. THIS SHALL BE |
| | VERIFIED AND REVISED ACCORDINGLY. |
| | |
| | 3) NOTE: PLEASE SEE NOTE ON PLANS MENTIONS THE DISPOSAL |
| | AND DISHWASHER ARE FED TO THE SAME UNDER COUNTER |
| | RECEPTACLE HOWEVER THE PLANS AT THIS SAME LOCATION |
| | INDICATE SEPARATE RECEPTACLES ON EITHER SIDE OF THE |
| | SINK. |
| | THIS NEEDS TO BE VERIFIED. IF THESE ARE BOTH FED TO THE |
| | SAME RECEPTACLE DEVICE THAN THE 1-POLEBREAKERS ON |
| | PANEL SCHEDULE FOR CIRCUITS 10 AND 12 WILL BE REQUIRED |
| | TO BE CHANGED TO A 2-POL BREAKER PER 210.4B. |
| | |
| | ** NEED TO REVISE THE PLANS ALONG WITH ANY OTHER |
| | REVISIONS BEFORE ROUGH ELECTRICAL INSPECTION. A HOLD |
| | WILL BE PLACED ON THE INSPECTIONS. |
| | ** IF PLANS COME BACK WITH CORRECTIONS FOR ANY OTHER |
| | TRADES BEFORE PERMIT IS ISSUED PLEASE REVISE PLANS AT |
| | THAT TIME. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |