| Plan Review Notes For Permit 07061010 |
| Permit Number |
07061010 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-07-12 11:29:09 | DENIED; | | | 1. 1/2 BATHROOM; CHECK FOR CLEAR FLOOR SPACE IN FRONT | | | OF TOILET, MUST BE 21", SEE FBC PLUMBING SECTION | | | 405.3.1. | | | 2. SANITARY RISER DIAGRAM; | | | A) HORIZONTAL DRY VENT FOR MASTER TOILET NOT | | | PERMITED SECTION 905.3. | | | B) AUTOMATIC CLOTHES WASHER TO DISCHARGE | | | DOWN STREAM OF THE 1/2 BATH GROUP, SECTION 909.1 | | | C) THE TUB WASTE CANNOT RUN THRU THE SHOWER | | | TRAP AS DRAWN. SECTION 1002.1. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|