Plan Review Notes
Plan Review Notes For Permit 07061010
Permit Number 07061010
Review Stop P
Sequence Number 1
Notes
Date Text
2007-07-12 11:29:09DENIED;
 1. 1/2 BATHROOM; CHECK FOR CLEAR FLOOR SPACE IN FRONT
 OF TOILET, MUST BE 21", SEE FBC PLUMBING SECTION
 405.3.1.
 2. SANITARY RISER DIAGRAM;
 A) HORIZONTAL DRY VENT FOR MASTER TOILET NOT
 PERMITED SECTION 905.3.
 B) AUTOMATIC CLOTHES WASHER TO DISCHARGE
 DOWN STREAM OF THE 1/2 BATH GROUP, SECTION 909.1
 C) THE TUB WASTE CANNOT RUN THRU THE SHOWER
 TRAP AS DRAWN. SECTION 1002.1.