Plan Review Notes
Plan Review Notes For Permit 07061010
Permit Number 07061010
Review Stop M
Sequence Number 1
Notes
Date Text
2007-07-05 09:33:01*** DENIED ***
 1) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT
 ALSO, PER 2004 FBC 13-600.3.ABC.2.
  
 2) THE ENERGY CALCULATIONS ARE CALLING FOR A 16.5 SEER
 A/C SYSTEM, THE MECHANICAL PLANS ARE CALLING FOR A 13
 SEER A/C SYSTEM, THE TWO MUST COINCIDE PLEASE CORRECT.
  
 3) SHOW ON MECHANICAL PLANS THE HEATER SIZE (KW).
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.