| Plan Review Notes For Permit 07061010 |
| Permit Number |
07061010 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-07-05 09:33:01 | *** DENIED *** | | | 1) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT | | | ALSO, PER 2004 FBC 13-600.3.ABC.2. | | | | | | 2) THE ENERGY CALCULATIONS ARE CALLING FOR A 16.5 SEER | | | A/C SYSTEM, THE MECHANICAL PLANS ARE CALLING FOR A 13 | | | SEER A/C SYSTEM, THE TWO MUST COINCIDE PLEASE CORRECT. | | | | | | 3) SHOW ON MECHANICAL PLANS THE HEATER SIZE (KW). | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|