Plan Review Notes
Plan Review Notes For Permit 07061010
Permit Number 07061010
Review Stop E
Sequence Number 1
Notes
Date Text
2007-07-03 18:50:39* UNSAT **
  
 1) NOTE: 1) NOTE: PLEASE SEE THE SUBMITTED DOCUMENTS
 REQUIRE THE CODES TO BE STATED ON PLANS. PLEASE SEE THE
 FOLLOWING ARE REQUIRED FOR ELECTRICAL AND OTHERS WILL
 BE REQUIRED FOR OTHER TRADES. PLEASE KNOW AS OF
 DECEMBER 8TH, 2006 THE STATE ADOPTED THE 2006 REVISIONS
 TO THE 2004 FBC.
 PLEASE LIST THE FOLLOWING
 2004 FBC W/ 2006 REVISIONS.
 2005 NFPA-70 (ALREADY SHOWN)
 2003 NFPA-101
 2002 NFPA-72
  
 2) NOTE: PLEASE CLARIFY SERVICE AS RISER APPEARS TO
 SHOW AND INDICATE SOME AS NEW AND THE LOAD CALCULATIONS
 INDICATE SERVICE AS EXISTING?
 PLEASE SEE RISER SHOWS A MAIN DISCONNECT, HOWEVER PLANS
 DO NOT INDICATE THIS MAIN OUTSIDE?
 110.26, 230.70 ETC
 PLEASE SEE NOTE #7 ALSO.
  
 3) NOTE: PLEASE SEE PANEL SCHEDULE CONTAINS NOTE WHICH
 MENTIONS PANEL IS IN GARAGE HOWEVER PLEASE SEE THE
 PLANS AS THEY DO NOT INDICATE ANY PANEL IN GARAGE.
 PLEASE INDICATE ALL SERVICE EQUIPMENT AND PANEL(S) ON
 PLANS.
 110.26,240.24,408.7, ETC
 FBC 106.1.2, 106.3.5.4
  
 4) NOTE: PLEASE SEE PLANS ARE MISSING CIRCUITING ON
 SEVERAL ITEMS. PLEASE SEE GFI RECEPTACLES REAR WALLS,
 FLOOD LTS (NOT ALL), SMOKE ALARMS, INSTA-GAS WH, ETC.
 PLEASE SEE THERE ARE DEVICES INSIDE DWELLING AS WELL.
 PLEASE COMPLETE AND COORDINATE WITH THE PANEL
 SCHEDULE.
 408.4, 310.16, 24.4
 FBC 106.3.5.4
  
 5) NOTE: PLEASE SEE MISSING ARC FAULT FOR SMOKE ALARMS
 ONCE CIRCUITED. 210.12
  
 6) NOTE: PLEASE SEE NFPA-72 11-5.1.1.1 AND 11.8.3 AS
 THE LOCATION OF THE SA IN THE MASTER BEDROOM NEEDS TO
 BE RELOCATED INTO THE BEDROOM AREA OR ADD AN ADDITIONAL
 UNIT.
  
 7) NOTE: PLEASE SEE BASED ON THE RISER AND THE SERVICE
 ENTRANCE CONDUCTORS THE GROUNDING ELECTRODE CONDUCTOR
 IS NOT OF SUFFICIENT SIZE BASED ON 250.66
 PLEASE INCREASE/ADJUST.
  
 8) NOTE: PLEASE SEE SOME MISSING RECEPTACLES FOR 2FT OR
 MORE OF WALL SPACE AND RECEPTACLES WITHIN 12FT OF EACH
 OTHER. PLEASE SEE LIVING AND DINING WALLS.
 210.52
  
 9) NOTE: PLEASE SEE ALL RECESSED LIGHTING LUMINARIES
 ARE REQUIRED TO MEET FBC 2004 13-606.1.ABC.1.2.4.
 PLEASE PLACE NOTE/INFORMATION FOR THIS.
  
 10) NOTE: PLEASE SEE 410.8 FOR RECESSED LIGHTING SHOWN
 OVER JACUZZI TUB. PLEASE SPECIFY THE TYPE OF FIXTURE AS
 THERE ARE SOME FIXTURES WHICH ARE LISTED TO BE OVER TUB
 W/OUT BEING A CLOSED IN TYPE VAPOR PROOF. IF USING VP,
 THEN INDICATE. PLEASE KNOW IN ANY CASE NO FIXTURES MAY
 BE WITHIN 7FT OF THE HIGHEST WATER LEVEL.
 PLEASE ADJUST TYPE FIXTURE.
  
 11) NOTE: PLEASE SEE NO GFI PROTECTION IS INDICATED ON
 PLANS OR PANEL SCHEDULE FOR THE JACUZZI TUB.
 PLEASE SEE 680.71
  
 12) NOTE: PLEASE SEE 210.52B1, AND 220.52 AS THE DINING
 ROOM/AREA RECEPTACLES ARE NOT PERMITTED TO BE ON WITH
 THE LIVING ROOM AS SHOWN. PLEASE SEE THE CODE SECTIONS
 GIVEN AS ONE OR MORE OF THE SMALL APPLIANCE CIRCUITS
 SHALL BE A MINIMUM OF 1500VA.
 PLEASE SEE THE DINING/BREAKFAST AREAS AND THE LIKE
 SHALL BE INCLUDED.
  
 13) NOTE: PLEASE CORRELATE ALL LOAD CALCULATIONS INTO
 ONE LOAD CALCULATION OF EXISTING AND NEW. PLEASE SEE
 SOME ITEMS ON PLANS WHICH ARE DEDICATED CIRCUITS ARE
 NOT IN LOAD CALCULATIONS OR LOADS DO NOT COORDINATE.
 PLEASE SEE RANGE (LOAD), SEE MISSING GDO LOAD/CIRCUIT
 ON PANEL SCHEDULE, SEE MISSING MULTIPLE SMALL APPLIANCE
 CIRCUITS ABOVE ETC.
 PLEASE ALSO SEE 220.83 ETC.
  
 14) NOTE: PLEASE KNOW THE LOW VOLTAGE AS SHOWN ON PLANS
 WILL BE REQUIRED TO BE UNDER A SEPARATE PERMIT. THE
 SEPARATE PERMIT APPLICATION MAY REFERENCE THESE PLANS
 FOR CATV, PHONE AS SHOWN ON PLANS.
 PLEASE KNOW THAT ANY LV FOR SECURITY/ALARM WILL BE
 REQUIRED TO BE UNDER SEPARATE PERMIT, HOWEVER NOT PLANS
 ARE NEEDED.
  
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT ELECTRICAL PLANS AND DESIGN CHANGES.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT ELECTRICAL PLANS AND DESIGN CHANGES.
  