| 2007-07-03 18:50:39 | * UNSAT ** |
| | |
| | 1) NOTE: 1) NOTE: PLEASE SEE THE SUBMITTED DOCUMENTS |
| | REQUIRE THE CODES TO BE STATED ON PLANS. PLEASE SEE THE |
| | FOLLOWING ARE REQUIRED FOR ELECTRICAL AND OTHERS WILL |
| | BE REQUIRED FOR OTHER TRADES. PLEASE KNOW AS OF |
| | DECEMBER 8TH, 2006 THE STATE ADOPTED THE 2006 REVISIONS |
| | TO THE 2004 FBC. |
| | PLEASE LIST THE FOLLOWING |
| | 2004 FBC W/ 2006 REVISIONS. |
| | 2005 NFPA-70 (ALREADY SHOWN) |
| | 2003 NFPA-101 |
| | 2002 NFPA-72 |
| | |
| | 2) NOTE: PLEASE CLARIFY SERVICE AS RISER APPEARS TO |
| | SHOW AND INDICATE SOME AS NEW AND THE LOAD CALCULATIONS |
| | INDICATE SERVICE AS EXISTING? |
| | PLEASE SEE RISER SHOWS A MAIN DISCONNECT, HOWEVER PLANS |
| | DO NOT INDICATE THIS MAIN OUTSIDE? |
| | 110.26, 230.70 ETC |
| | PLEASE SEE NOTE #7 ALSO. |
| | |
| | 3) NOTE: PLEASE SEE PANEL SCHEDULE CONTAINS NOTE WHICH |
| | MENTIONS PANEL IS IN GARAGE HOWEVER PLEASE SEE THE |
| | PLANS AS THEY DO NOT INDICATE ANY PANEL IN GARAGE. |
| | PLEASE INDICATE ALL SERVICE EQUIPMENT AND PANEL(S) ON |
| | PLANS. |
| | 110.26,240.24,408.7, ETC |
| | FBC 106.1.2, 106.3.5.4 |
| | |
| | 4) NOTE: PLEASE SEE PLANS ARE MISSING CIRCUITING ON |
| | SEVERAL ITEMS. PLEASE SEE GFI RECEPTACLES REAR WALLS, |
| | FLOOD LTS (NOT ALL), SMOKE ALARMS, INSTA-GAS WH, ETC. |
| | PLEASE SEE THERE ARE DEVICES INSIDE DWELLING AS WELL. |
| | PLEASE COMPLETE AND COORDINATE WITH THE PANEL |
| | SCHEDULE. |
| | 408.4, 310.16, 24.4 |
| | FBC 106.3.5.4 |
| | |
| | 5) NOTE: PLEASE SEE MISSING ARC FAULT FOR SMOKE ALARMS |
| | ONCE CIRCUITED. 210.12 |
| | |
| | 6) NOTE: PLEASE SEE NFPA-72 11-5.1.1.1 AND 11.8.3 AS |
| | THE LOCATION OF THE SA IN THE MASTER BEDROOM NEEDS TO |
| | BE RELOCATED INTO THE BEDROOM AREA OR ADD AN ADDITIONAL |
| | UNIT. |
| | |
| | 7) NOTE: PLEASE SEE BASED ON THE RISER AND THE SERVICE |
| | ENTRANCE CONDUCTORS THE GROUNDING ELECTRODE CONDUCTOR |
| | IS NOT OF SUFFICIENT SIZE BASED ON 250.66 |
| | PLEASE INCREASE/ADJUST. |
| | |
| | 8) NOTE: PLEASE SEE SOME MISSING RECEPTACLES FOR 2FT OR |
| | MORE OF WALL SPACE AND RECEPTACLES WITHIN 12FT OF EACH |
| | OTHER. PLEASE SEE LIVING AND DINING WALLS. |
| | 210.52 |
| | |
| | 9) NOTE: PLEASE SEE ALL RECESSED LIGHTING LUMINARIES |
| | ARE REQUIRED TO MEET FBC 2004 13-606.1.ABC.1.2.4. |
| | PLEASE PLACE NOTE/INFORMATION FOR THIS. |
| | |
| | 10) NOTE: PLEASE SEE 410.8 FOR RECESSED LIGHTING SHOWN |
| | OVER JACUZZI TUB. PLEASE SPECIFY THE TYPE OF FIXTURE AS |
| | THERE ARE SOME FIXTURES WHICH ARE LISTED TO BE OVER TUB |
| | W/OUT BEING A CLOSED IN TYPE VAPOR PROOF. IF USING VP, |
| | THEN INDICATE. PLEASE KNOW IN ANY CASE NO FIXTURES MAY |
| | BE WITHIN 7FT OF THE HIGHEST WATER LEVEL. |
| | PLEASE ADJUST TYPE FIXTURE. |
| | |
| | 11) NOTE: PLEASE SEE NO GFI PROTECTION IS INDICATED ON |
| | PLANS OR PANEL SCHEDULE FOR THE JACUZZI TUB. |
| | PLEASE SEE 680.71 |
| | |
| | 12) NOTE: PLEASE SEE 210.52B1, AND 220.52 AS THE DINING |
| | ROOM/AREA RECEPTACLES ARE NOT PERMITTED TO BE ON WITH |
| | THE LIVING ROOM AS SHOWN. PLEASE SEE THE CODE SECTIONS |
| | GIVEN AS ONE OR MORE OF THE SMALL APPLIANCE CIRCUITS |
| | SHALL BE A MINIMUM OF 1500VA. |
| | PLEASE SEE THE DINING/BREAKFAST AREAS AND THE LIKE |
| | SHALL BE INCLUDED. |
| | |
| | 13) NOTE: PLEASE CORRELATE ALL LOAD CALCULATIONS INTO |
| | ONE LOAD CALCULATION OF EXISTING AND NEW. PLEASE SEE |
| | SOME ITEMS ON PLANS WHICH ARE DEDICATED CIRCUITS ARE |
| | NOT IN LOAD CALCULATIONS OR LOADS DO NOT COORDINATE. |
| | PLEASE SEE RANGE (LOAD), SEE MISSING GDO LOAD/CIRCUIT |
| | ON PANEL SCHEDULE, SEE MISSING MULTIPLE SMALL APPLIANCE |
| | CIRCUITS ABOVE ETC. |
| | PLEASE ALSO SEE 220.83 ETC. |
| | |
| | 14) NOTE: PLEASE KNOW THE LOW VOLTAGE AS SHOWN ON PLANS |
| | WILL BE REQUIRED TO BE UNDER A SEPARATE PERMIT. THE |
| | SEPARATE PERMIT APPLICATION MAY REFERENCE THESE PLANS |
| | FOR CATV, PHONE AS SHOWN ON PLANS. |
| | PLEASE KNOW THAT ANY LV FOR SECURITY/ALARM WILL BE |
| | REQUIRED TO BE UNDER SEPARATE PERMIT, HOWEVER NOT PLANS |
| | ARE NEEDED. |
| | |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES |
| | WHICH MAY AFFECT ELECTRICAL PLANS AND DESIGN CHANGES. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES |
| | WHICH MAY AFFECT ELECTRICAL PLANS AND DESIGN CHANGES. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |