| 2007-08-20 09:35:04 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| | CODE |
| | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* |
| | CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC |
| | FLORIDA ADMINISTRATIVE CODE |
| | FSFLORIDA STATUTE |
| | |
| | |
| | _XX_4.IMPACT PROTECTION REQUIRED,FBC1609.1.4, FBC R |
| | 301.2.1.2.PROVIDE PRODUCT APPROVALS AND, IF SHUTTERS |
| | ARE USED, COMPLETE THE ATTACHED INSTALLATION SCHEDULE. |
| | |
| | CONTRACTOR RESUBMITTED WITH A NOTE ON THE RESUB SHEET |
| | "PER PLAN REVIEWER SAMANTHA HILL THIS INSTALLATION |
| | MEETS THE REQUIREMENT FOR THE FBC 25% RULE EXCEPTION." |
| | |
| | |
| | PLEASE NOTE THAT I DO NOT DETERMINE WHICH JOBS FALL |
| | UNDER THIS EXCEPTION.THE CONTRACTOR IS TO PROVIDE |
| | ENOUGH INFORMATION TO SHOW CODE COMPLIANCE ON THE PLAN. |
| | PROVIDE INFORMATION ABOUT THE EXISTING DOOR (SQUARE |
| | FOOT AREA OF GLASS IN THE EXISTING DOOR), GLASS AREA IN |
| | THE NEW DOOR, AGGREGATE GLAZED AREA OF THE HOUSE, SHOW |
| | COMPLIANCE WITH 25% EXCEPTION FBC EB 507.3.THE RESUB |
| | SHEET IS NOT A PART OF THE PERMIT PACKAGE, DOES NOT |
| | SHOW CODE COMPLIANCE, AND I DO NOT DETERMINE WHAT JOB |
| | CONDITIONS ARE; THE CONTRACTOR DOES.PLEASE CONTACT ME |
| | IF YOU NEED ASSISTANCE IN DETERMINING HOW TO REVISE THE |
| | PLAN. |
| | |