| Notes |
| Date |
Text |
| 2007-07-26 14:17:39 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | FAC FLORIDA ADMINISTRATIVE CODE | | | FSFLORIDA STATUTE | | | | | | 1.)THE PRODUCT APPROVAL IS FOR A REROOF, YOU | | | APPLICATION IS FOR RECOVER. | | | | | | 2.)THE ENHANCED FASTENING FOR ZONES 2 AND 3 ARE TO BE | | | INCORPORATED INTO THE PERMIT PACKAGE (NOT SPECIFIED ON | | | THE APPLICATION).THIS CAN BE DONE WITH ENGINEERING, | | | BY THE CONTRACTOR ON LETTERHEAD, WRITTEN ON THE PRODUCT | | | APPROVAL, OR ANOTHER METHOD WHICH IS INCORPORATED INTO | | | THE PLANS. | | | | | | 3.)THE APPLICATION SPECIFIES 5 FASTENERS PER BOARD. | | | IT IS NOT CLEAR IF THIS IS FOR THE FIELD, ZONE 2, ZONE | | | 3, OR ALL ZONES.PLEASE SEE ITEM 2 AND PROVIDE ALL | | | INFORMATION IN A FORMAT WHICH CAN BE INCORPORATED INTO | | | THE PLAN. | | | | | | 4.)SPECIFY ENHANCED FASTENING FOR BOTH THE INSULATION | | | BOARD AND THE MEMBRANE AS DISCUSSED. | | | | | | 5.)THE PERMIT APPLICATION IS TO INCLUDE ROOF DECK | | | TYPE AND THE MEAN ROOF HEIGHT. | | | |
|