| Plan Review Notes For Permit 07060881 |
| Permit Number |
07060881 |
|
| Review Stop |
B |
| Sequence Number |
5 |
|
| Notes |
| Date |
Text |
| 2009-06-25 18:24:50 | REVISION DATED 4/25/9 | | | COMMENT LIST REVISED 7/8/9 | | | | | | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2004 | | | FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL | | | | | | 1. M2.01, DETAIL FOR SECURING CONDENSING IS NOT CLEAR. | | | TWO BRACKETS ARE GRAPHICALLY SHOWN ON ONE SIDE OF THE | | | UNIT, BUT THE TEXT SPECIFIES 4. IF FOUR ARE INSTALLED, | | | TWO PER SIDE, THIS LEAVES TWO SIDES WITHOUT BRACKETS, | | | NOT CLEAR HOW THOSE TWO SIDES WILL RESIST WIND | | | PRESSURES. | | | | | | PLEASE DO NOT RESUBMIT THE MECHANICAL SHEETS. EITHER | | | PROVIDE A NEW DETAIL OR THIS WILL BE PROVISO ITEM, | | | INSTALL IN ACCORDANCE WITH FBC R301, SUBJECT TO | | | INSPECTOR'S DISCRETION. | | | | | | 2. R703.6.3, DETAIL 4 A5 DOES NOT SHOW REQUIRED BOND | | | BREAK. ***IF PLANS DO NOT NEED TO BE REVISED FOR OTHER | | | REASONS, THIS WILL BE A REDLINE ITEM*** | | | | | | 3. A NEW WINDOW OPENING IS SHOWN, PLEASE PROVIDE | | | FRAMING DETAIL FBC R301. ***IF PLANS DO NOT REQUIRE | | | REVISION FOR OTHER REASONS, THIS WILL BE A PROVISO | | | ITEM.** | | | | | | 4. A4 STATES TO REPLACE EXIST NON ORIGINAL ALUMINUM | | | CASEMENT WINDOW WITH AN ALUMINUM AWNING WINDOW, REUSED. | | | FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED FOR | | | THE INSTALLED WINDOW, FAC9B72. | | | | | | |
|