2009-06-25 18:24:50REVISION DATED 4/25/9
 COMMENT LIST REVISED 7/8/9
  
 ****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2004
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
  
 1. M2.01, DETAIL FOR SECURING CONDENSING IS NOT CLEAR.
 TWO BRACKETS ARE GRAPHICALLY SHOWN ON ONE SIDE OF THE
 UNIT, BUT THE TEXT SPECIFIES 4. IF FOUR ARE INSTALLED,
 TWO PER SIDE, THIS LEAVES TWO SIDES WITHOUT BRACKETS,
 NOT CLEAR HOW THOSE TWO SIDES WILL RESIST WIND
 PRESSURES.
  
 PLEASE DO NOT RESUBMIT THE MECHANICAL SHEETS. EITHER
 PROVIDE A NEW DETAIL OR THIS WILL BE PROVISO ITEM,
 INSTALL IN ACCORDANCE WITH FBC R301, SUBJECT TO
 INSPECTOR'S DISCRETION.
  
 2. R703.6.3, DETAIL 4 A5 DOES NOT SHOW REQUIRED BOND
 BREAK. ***IF PLANS DO NOT NEED TO BE REVISED FOR OTHER
 REASONS, THIS WILL BE A REDLINE ITEM***
  
 3. A NEW WINDOW OPENING IS SHOWN, PLEASE PROVIDE
 FRAMING DETAIL FBC R301. ***IF PLANS DO NOT REQUIRE
 REVISION FOR OTHER REASONS, THIS WILL BE A PROVISO
 ITEM.**
  
 4. A4 STATES TO REPLACE EXIST NON ORIGINAL ALUMINUM
 CASEMENT WINDOW WITH AN ALUMINUM AWNING WINDOW, REUSED.
 FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED FOR
 THE INSTALLED WINDOW, FAC9B72.
  
  