Plan Review Notes
Plan Review Notes For Permit 07060881
Permit Number 07060881
Review Stop B
Sequence Number 2
Notes
Date Text
2007-10-02 18:57:59 
  
 DENIED
  
 THE FOLLOWING COMMENTS WERE NOT ADDRESSED FROM 1ST
 REVIEW ON 7/14/07:
  
 5)SUBMIT TWO COPIES OF ENERGY CALC'S PER 13-101.2.2
 FBC. BE SURE THAT THEY ARE SIGNED AND DATED BY PREPARER
 AND OWNER/AGENT PRIOR TO SUBMITTAL
 ****NOTE MAKE THE FOLLWING CORRECTIONS TO ENERGY
 CALC'S, WALLS ARE WOOD FRAME NOT CONCRETE, THEY ARE NOT
 SIGNED BY OWNER AGENT, AND UNLESS COMPLETE HOUSE IS
 BEING BROUGHT UP TO NEW ENERGY STANDARDS FORM 600C-04R
 SHOULD BE USED FOR ADDITIONS OR RENOVATIONS 600 SQ. FT.
 OR LESS****
  
 7)PLANS AND SPECIFICATIONS DESIGN PARAMETERS SHALL
 COMPLY WITH THE 2004 FLORIDA BLDG CODE WITH 2006
 AMENDMENTS PER 106.1.1 FBC*
 ****NOTE THIS SHALL BE INCUDED ON THE PERMIT SET OF
 DRAWINGS****
  
 8)IN AN EXISTING BUILDING WHERE ALTERATIONS ARE BEING
 MADE A DESIGN PROFESSIONAL MUST ELECT THE LEVEL OF
 ALTERATION PER 301.5 OF EXISTING BUILDING CODE AND
 STATE ALONG WITH THE TYPE OF CONSTRUCTION ON THE
 DRAWINGS
 ****NOTE ALTERATION LEVEL FITS THE DEFINITION OF A
 LEVEL 2, PLEASE SEE ATTACHED COPY OF CHAPTER 3
 CLASSIFICATION OF WORK****
  
 NEW COMMENTS
  
 1)PROVIDE PRODUCT APPROVALS FOR THE NEW FRONT ENTRY
 DOOR
  
 2)NEW NOTE UNDER WINDOW SCHEDULE ON A-3 IS INCORRECT
 PLEASE REMOVE, ALL OPENINGS WITHIN 30 FEET OF GRADE
 SHALL MEET LARGE MISSILE IMPACT REQUIREMENTS PER
 1609.1.4 (1) FBC
  
 3)PROVIDE PRODUCT APPROVALS FOR SHUTTERS FOR WINDOWS
 IN NEW LOCATIONS
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  
  
  
  
  
  
  
  
  
  
  
  
  
  