| Notes |
| Date |
Text |
| 2007-06-29 08:59:10 | | | | | | | NONCOMPLIANT | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE | | | COMPLIANCE AND RESUBMIT FOR REVIEW. | | | | | | 1} PROVIDE LOAD CALCULATIONS, INCLUDE ADDED LOADS, PER | | | ARTICLE 220 PART III, STANDARD OR PART IV OPTIONAL, | | | INDICATE METHOD USED, INDICATE THE SIZE OF THE EXISTING | | | SERVICE. INDICATE THE SIZE AND TYPE OF THE SERVICE | | | ENTRANCE CONDUCTORS ON THE RISER DIAGRAM, SHEET E2.01. | | | PER 215.5. | | | | | | 2} SUBMIT A PANEL SCHEDULE PER 408.4 NEC AND | | | 106.3.5.4(8) FBC.THE ONE SUBMITTED DOESNT CORRELATE THE | | | LOADS WITH THE EQUIPMENT. SHEET E2.01. | | | | | | 3} R313.1.1 SMOKE ALARMS SHALL BE LOCATED AS REQUIRED | | | IN NEW DWELLINGS WHEN REPAIRS OR ADDITIONS REQUIRING A | | | PERMIT OCCUR. SEE ARTICLE FOR COMPLETE TEXT.LOCATE SAME | | | ON THE PLAN. | | | | | | 4} THE SCUTTLE FOR AHU 1 MUST COMPLY WITH 210.63 | | | (RECEPTACLE). | | | | | | 5} THE LOCATION OF THE NEW A/C SERVICE PANEL MUST | | | COMPLY WITH 110.26 CLEARANCE REQUIREMENTS. IT WOULD | | | APPEAR IT IS LOCATED OVER THE CONDENSER PAD , WHICH | | | WOULD BE A VIOLATION. PLEASE VERIFY AND RELOCATE NOW IF | | | NECESSARY TO PREVENT AN INSPECTION ISSUE AFTER THE | | | EQUIPMENT IS INSTALLED. | | | | | | NOTE: PLEASE VERIFY THAT THE NEW PANEL WILL BE FED FROM | | | THE METER AND NOT SUBFED FROM THE EXISTING PANEL. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW. | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | [email protected] |
|