2007-06-29 08:59:10 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} PROVIDE LOAD CALCULATIONS, INCLUDE ADDED LOADS, PER
 ARTICLE 220 PART III, STANDARD OR PART IV OPTIONAL,
 INDICATE METHOD USED, INDICATE THE SIZE OF THE EXISTING
 SERVICE. INDICATE THE SIZE AND TYPE OF THE SERVICE
 ENTRANCE CONDUCTORS ON THE RISER DIAGRAM, SHEET E2.01.
 PER 215.5.
  
 2} SUBMIT A PANEL SCHEDULE PER 408.4 NEC AND
 106.3.5.4(8) FBC.THE ONE SUBMITTED DOESNT CORRELATE THE
 LOADS WITH THE EQUIPMENT. SHEET E2.01.
  
 3} R313.1.1 SMOKE ALARMS SHALL BE LOCATED AS REQUIRED
 IN NEW DWELLINGS WHEN REPAIRS OR ADDITIONS REQUIRING A
 PERMIT OCCUR. SEE ARTICLE FOR COMPLETE TEXT.LOCATE SAME
 ON THE PLAN.
  
 4} THE SCUTTLE FOR AHU 1 MUST COMPLY WITH 210.63
 (RECEPTACLE).
  
 5} THE LOCATION OF THE NEW A/C SERVICE PANEL MUST
 COMPLY WITH 110.26 CLEARANCE REQUIREMENTS. IT WOULD
 APPEAR IT IS LOCATED OVER THE CONDENSER PAD , WHICH
 WOULD BE A VIOLATION. PLEASE VERIFY AND RELOCATE NOW IF
 NECESSARY TO PREVENT AN INSPECTION ISSUE AFTER THE
 EQUIPMENT IS INSTALLED.
  
 NOTE: PLEASE VERIFY THAT THE NEW PANEL WILL BE FED FROM
 THE METER AND NOT SUBFED FROM THE EXISTING PANEL.
  