Plan Review Notes
Plan Review Notes For Permit 07060876
Permit Number 07060876
Review Stop E
Sequence Number 1
Notes
Date Text
2007-06-29 18:43:50 
  
 *** UNSAT ***
  
 *** PLEASE NOTE: AS THERE IS INFORMATION NOT YET
 SUBMITTED FOR REVIEW, THERE MAY VERY WELL BE NEW
 COMMENTS ON THE NEXT REVIEW AS THESE ITEMS CAN NOT BE
 REVIEWED AT THIS TIME.
  
  
 1) NOTE: PLEASE SEE THE SUBMITTED DOCUMENTS REQUIRE THE
 CODES TO BE STATED ON PLANS. PLEASE SEE THE FOLLOWING
 ARE REQUIRED FOR ELECTRICAL AND OTHERS WILL BE REQUIRED
 FOR OTHER TRADES. PLEASE KNOW AS OF DECEMBER 8TH, 2006
 THE STATE ADOPTED THE 2006 REVISIONS TO THE 2004 FBC
 AND THE 2005 NFPA-70. PLEASE LIST THE FOLLOWING 2004
 FBC W/ 2006 REVISIONS.
 2005 NFPA-70
 2003 NFPA-101
 2002 NFPA-72
  
 2) NOTE: PLEASE KNOW THAT PERMIT APPLICATION WAS
 SUBMITTED WITHOUT ANY SUITE/UNIT/SPACE #. PLEASE KNOW
 THAT A COPY OF THE PERMIT APPLICATION HAS BEEN
 FORWARDED TO THE ADDRESSING REVIEWER. ONCE THE
 SUITE/UNIT/SPACE NUMBER HAS BEEN DETERMINED PLEASE BE
 SURE THIS INFORMATION IS PLACED ON PLANS/TITLE BLOCKS.
 FAC 61G15-23.002, 61G1-16.004
  
 3) NOTE:PLEASE SEE THERE ARE DISCREPANCIES WITH THE
 PERMIT APPLICATION AND THE PLANS AS SUBMITTED. PLEASE
 SEE PERMIT APPLICATION MENTIONS *DEMOLISH SOME
 PARTITIONS* HOWEVER THE PLANS ALSO INCLUDE SOME SHEETS
 FOR NEW WORK?
 PLEASE CLARIFY.
 FBC 106.1, 106.3.5.1.2
  
  
 4) NOTE: PLEASE SEE THE INFORMATION AS STATED ON TITLE
 BLOCKS FOR THE ARCHITECTURAL FIRM DOES NOT CORRELATE
 WITH THE STATE DEPARTMENT OF BUSINESS AND PROFESSIONAL
 REGULATION. PLEASE SEE I HAVE ATTACHED THE PRINT OUT AS
 OF THIS REVIEWFROM DBPR WHICH SHOWS DIFFERENT LICENSE
 INFORMATION THAN THAT ONE PLANS.
 ** PLEASE KNOW THIS IS REQUIRED OF ALL SHEETS AND FOR
 ALL TRADES WHETHER OR NOT COMMENT IS MADE BY OTHER
 TRADE(S).
 FAC 61G1-16.004, FS 481.219
  
 5) NOTE: PLEASE SUBMIT ELECTRICAL PLANS FOR NEW WORK.
 PLEASE SEE THE 2004 FBC ESPECIALLY CHAPTER 13. PLEASE
 SEE THE 2005 NEC FOR OTHER ITEMS RELATED TO DESIGN AS
 WELL AS NFPA-101 AND NFPA-72
  
 6) NOTE: PLEASE SEE FBC 11-4.28.1, .2 AND .3(4) FOR
 MINIMUM LEVELS FOR FIRE ALARMS DEVICES TO BE STATED FOR
 ANY CHANGES. PLEASE SHOW ANY NEW EXISTING WHICH MEETS
 THIS SECTION WHERE WORK IS BEING AND CHANGES ARE BEING
 MADE.
  
 7) NOTE: PLEASE SEE THE VALUE ON PERMIT APPLICATION IS
 YET TO BE CONFIRMED UNTIL CLARIFICATION OF THE SCOPE OF
 WORK.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT ELECTRICAL PLANS AND DESIGN CHANGES.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]