| 2007-06-29 18:43:50 | |
| | |
| | *** UNSAT *** |
| | |
| | *** PLEASE NOTE: AS THERE IS INFORMATION NOT YET |
| | SUBMITTED FOR REVIEW, THERE MAY VERY WELL BE NEW |
| | COMMENTS ON THE NEXT REVIEW AS THESE ITEMS CAN NOT BE |
| | REVIEWED AT THIS TIME. |
| | |
| | |
| | 1) NOTE: PLEASE SEE THE SUBMITTED DOCUMENTS REQUIRE THE |
| | CODES TO BE STATED ON PLANS. PLEASE SEE THE FOLLOWING |
| | ARE REQUIRED FOR ELECTRICAL AND OTHERS WILL BE REQUIRED |
| | FOR OTHER TRADES. PLEASE KNOW AS OF DECEMBER 8TH, 2006 |
| | THE STATE ADOPTED THE 2006 REVISIONS TO THE 2004 FBC |
| | AND THE 2005 NFPA-70. PLEASE LIST THE FOLLOWING 2004 |
| | FBC W/ 2006 REVISIONS. |
| | 2005 NFPA-70 |
| | 2003 NFPA-101 |
| | 2002 NFPA-72 |
| | |
| | 2) NOTE: PLEASE KNOW THAT PERMIT APPLICATION WAS |
| | SUBMITTED WITHOUT ANY SUITE/UNIT/SPACE #. PLEASE KNOW |
| | THAT A COPY OF THE PERMIT APPLICATION HAS BEEN |
| | FORWARDED TO THE ADDRESSING REVIEWER. ONCE THE |
| | SUITE/UNIT/SPACE NUMBER HAS BEEN DETERMINED PLEASE BE |
| | SURE THIS INFORMATION IS PLACED ON PLANS/TITLE BLOCKS. |
| | FAC 61G15-23.002, 61G1-16.004 |
| | |
| | 3) NOTE:PLEASE SEE THERE ARE DISCREPANCIES WITH THE |
| | PERMIT APPLICATION AND THE PLANS AS SUBMITTED. PLEASE |
| | SEE PERMIT APPLICATION MENTIONS *DEMOLISH SOME |
| | PARTITIONS* HOWEVER THE PLANS ALSO INCLUDE SOME SHEETS |
| | FOR NEW WORK? |
| | PLEASE CLARIFY. |
| | FBC 106.1, 106.3.5.1.2 |
| | |
| | |
| | 4) NOTE: PLEASE SEE THE INFORMATION AS STATED ON TITLE |
| | BLOCKS FOR THE ARCHITECTURAL FIRM DOES NOT CORRELATE |
| | WITH THE STATE DEPARTMENT OF BUSINESS AND PROFESSIONAL |
| | REGULATION. PLEASE SEE I HAVE ATTACHED THE PRINT OUT AS |
| | OF THIS REVIEWFROM DBPR WHICH SHOWS DIFFERENT LICENSE |
| | INFORMATION THAN THAT ONE PLANS. |
| | ** PLEASE KNOW THIS IS REQUIRED OF ALL SHEETS AND FOR |
| | ALL TRADES WHETHER OR NOT COMMENT IS MADE BY OTHER |
| | TRADE(S). |
| | FAC 61G1-16.004, FS 481.219 |
| | |
| | 5) NOTE: PLEASE SUBMIT ELECTRICAL PLANS FOR NEW WORK. |
| | PLEASE SEE THE 2004 FBC ESPECIALLY CHAPTER 13. PLEASE |
| | SEE THE 2005 NEC FOR OTHER ITEMS RELATED TO DESIGN AS |
| | WELL AS NFPA-101 AND NFPA-72 |
| | |
| | 6) NOTE: PLEASE SEE FBC 11-4.28.1, .2 AND .3(4) FOR |
| | MINIMUM LEVELS FOR FIRE ALARMS DEVICES TO BE STATED FOR |
| | ANY CHANGES. PLEASE SHOW ANY NEW EXISTING WHICH MEETS |
| | THIS SECTION WHERE WORK IS BEING AND CHANGES ARE BEING |
| | MADE. |
| | |
| | 7) NOTE: PLEASE SEE THE VALUE ON PERMIT APPLICATION IS |
| | YET TO BE CONFIRMED UNTIL CLARIFICATION OF THE SCOPE OF |
| | WORK. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES |
| | WHICH MAY AFFECT ELECTRICAL PLANS AND DESIGN CHANGES. |
| | |