| Plan Review Notes For Permit 07060850 |
| Permit Number |
07060850 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2008-02-12 13:39:03 | 2004 FBC W/2006 REVISIONS | | | | | | DENIED BY BUILDING | | | | | | 1) THE NOTICE OF COMMENCEMENT WILL NEED TO BE RECORDED | | | AND A COPY SUBMITTED. | | | | | | 2) PLEASE CLARIFY IF THE ROOF-CEILING CONSTRUCTION IS | | | CONVENTIONAL FRAMING OR SITE BUILT TRUSSES. IF THE ROOF | | | IS CONVENTIONAL FRAMING, SUBMIT DETAILS SHOWING THE | | | RAFTER, CEILING JOIST AND RIDGE SIZES AND CONNECTORS. | | | THE CONVENTIONAL ROOF FRAMING IS REQUIRED TO COMPLY | | | WITH THE IBHS GUIDELINE FOR HURRICANE RESISTANT | | | CONSTRUCTION OR ASCE7-02. | | | IF SITE BUILT-UP TRUSSES ARE USED, SUBMIT DETAILS FOR | | | THE SITE BUILT UP-TRUSSES. PROVIDE DETAILS FOR EACH | | | DIFFERENT TYPE OF TRUSS, SPECIFY THE LUMBER TYPE AND | | | SIZES FOR THE TOP AND BOTTOM CORDS AND WEBS. SPECIFY | | | HOW THE CORDS AND WEBS WILL BE CONNECTED TOGETHER. | | | PROVIDE ENGINEERING OR CALCULATIONS INDICATING THAT THE | | | TRUSSES ARE CAPABLE OFWITHSTANDING 140 MPH WINDLOADS. | | | FBC R 802.1 | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|