| 2007-07-11 10:03:49 | DENIED; | | | RISER DIAGRAM DOES NOT MEET CODE. | | | A) THE TUB IS NOT VENTED, THE LAV. VENT SHOULD BE | | | UP STREAM OF THE TUB. SEE FBC-2004 PLUMBING SECTION | | | 909.1. | | | B) THE AUTOMATIC CLOTHES WASHER BRANCH DRAIN TO | | | BE 3". FBC-2004 PLUMBING SECTION 406.3 | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|