| Plan Review Notes For Permit 07060850 |
| Permit Number |
07060850 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-07-05 08:48:36 | *** DENIED *** | | | 1) PROVIDE RETURN AIR FOR BEDROOM TO GET BACK TO AIR | | | HANDLER. | | | | | | 2) SHOW THE CFM'S AT ALL SUPPLY AIR GRILLS. | | | | | | 3) SHOW CLOTHES DRYER VENT ON MECHANICAL PLAN. | | | | | | 4) BE ADVISED MECHANICAL PLAN SHOWS NO SUPPLY AIR TO | | | THE COMPUTER AREA. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|