| Plan Review Notes For Permit 07060850 |
| Permit Number |
07060850 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-06-29 16:24:23 | | | | | | | NONCOMPLIANT | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE | | | COMPLIANCE AND RESUBMIT FOR REVIEW. | | | | | | 1} THERE IS NO INDICATION HOW THE "SUB-PANEL" IS FED. | | | PROVIDE A RISER DIAGRAM WITH CONDUCTOR AND CONDUIT SIZE | | | AND TYPE, GROUNDING DETAILS PER 215.5, 250.52 AND | | | 250.66. | | | | | | 2} THERE IS A CONDENSING UNIT ON THE PLAN, INDICATE IF | | | NEW OR RELOCATED. A RECEPTACLE IS REQUIRED PER 210.63. | | | | | | 3} THE 240 VOLT OUTLET AT THE CONDENSER NEEDS TO BE A | | | DISCONNECT PER 440.14. | | | | | | 4} A RECEPTACLE MUST BE ADDED IN THE BEDROOM PER | | | 210.52(A) SPACING REQUIREMENTS. | | | | | | 5} R313.1.1 SMOKE ALARMS SHALL BE LOCATED AS REQUIRED | | | IN NEW DWELLINGS WHEN REPAIRS OR ADDITIONS REQUIRING A | | | PERMIT OCCUR. SEE ARTICLE FOR COMPLETE TEXT. | | | SHOW LOCATIONS FOR COMPLIANCE ON THE PLAN. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 |
|