Plan Review Notes
Plan Review Notes For Permit 07060850
Permit Number 07060850
Review Stop E
Sequence Number 1
Notes
Date Text
2007-06-29 16:24:23 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} THERE IS NO INDICATION HOW THE "SUB-PANEL" IS FED.
 PROVIDE A RISER DIAGRAM WITH CONDUCTOR AND CONDUIT SIZE
 AND TYPE, GROUNDING DETAILS PER 215.5, 250.52 AND
 250.66.
  
 2} THERE IS A CONDENSING UNIT ON THE PLAN, INDICATE IF
 NEW OR RELOCATED. A RECEPTACLE IS REQUIRED PER 210.63.
  
 3} THE 240 VOLT OUTLET AT THE CONDENSER NEEDS TO BE A
 DISCONNECT PER 440.14.
  
 4} A RECEPTACLE MUST BE ADDED IN THE BEDROOM PER
 210.52(A) SPACING REQUIREMENTS.
  
 5} R313.1.1 SMOKE ALARMS SHALL BE LOCATED AS REQUIRED
 IN NEW DWELLINGS WHEN REPAIRS OR ADDITIONS REQUIRING A
 PERMIT OCCUR. SEE ARTICLE FOR COMPLETE TEXT.
 SHOW LOCATIONS FOR COMPLIANCE ON THE PLAN.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718