2007-08-10 17:16:30DENIED
 REFERENCE: FBC-2004 W/2006 AMENDMENTS
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. ALL "F" SHEETS. THE CERTIFICATE OF AUTHORIZATION IS
 REQUIRED TO BE IN THE TITLE BLOCK OF EACH SHEET. FAC
 61G15-23/002(2) & FS 471.025
  
 2. REFERENCE TO SOUTH FLORIDA BUILDING CODE IS NOT
 RELEVENT. PLEASE INDICATE CODE ADOPTED ON PLANS.
 FBC-2004 W/2006 AMENDMENTS
  
 3. SHT F-2 LINE SIZE TABLE (G) & FOUNTAIN PIPING PLAN.
 OVERFLOW SHALL DRAIN TO STORM, NOT SANITARY WASTE.
 PLEASE REVISE.
  
 4. SHT F-2 LINE SIZE TABLE (H) WATER SUPPLY LINE NOT
 FOUND ON PLAN. PLEASE CLARIFY. SECTION 106.1.1.
  
 5. SHT F-3 LINE SIZE TABLE (G) OVERFLOW SHALL DRAIN TO
 STORM, NOT SANITARY WASTE. PLEASE REVISE.
  
 6. SHT F-4 LINE SIZE TABLE (G) OVERFLOW SHALL DRAIN TO
 STORM, NOT SANITARY WASTE. PLEASE REVISE.
  
 7. PLANS SUBMITTED WITH REVISIONS TO THE BASE BUILDING
 SHALL BE SUBMITTED AS REVISIONS UNDER THE BLD-COM
 PERMIT NUMBER, NOT WITH THE FOUNTAIN APPLICATION.
 PLEASE SUBMIT REVISIONS UNDER THE CORRECT PERMIT
 NUMBER. (05091425).
  