| Plan Review Notes For Permit 07060848 |
| Permit Number |
07060848 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-08-10 17:16:30 | DENIED | | | REFERENCE: FBC-2004 W/2006 AMENDMENTS | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | | | | 1. ALL "F" SHEETS. THE CERTIFICATE OF AUTHORIZATION IS | | | REQUIRED TO BE IN THE TITLE BLOCK OF EACH SHEET. FAC | | | 61G15-23/002(2) & FS 471.025 | | | | | | 2. REFERENCE TO SOUTH FLORIDA BUILDING CODE IS NOT | | | RELEVENT. PLEASE INDICATE CODE ADOPTED ON PLANS. | | | FBC-2004 W/2006 AMENDMENTS | | | | | | 3. SHT F-2 LINE SIZE TABLE (G) & FOUNTAIN PIPING PLAN. | | | OVERFLOW SHALL DRAIN TO STORM, NOT SANITARY WASTE. | | | PLEASE REVISE. | | | | | | 4. SHT F-2 LINE SIZE TABLE (H) WATER SUPPLY LINE NOT | | | FOUND ON PLAN. PLEASE CLARIFY. SECTION 106.1.1. | | | | | | 5. SHT F-3 LINE SIZE TABLE (G) OVERFLOW SHALL DRAIN TO | | | STORM, NOT SANITARY WASTE. PLEASE REVISE. | | | | | | 6. SHT F-4 LINE SIZE TABLE (G) OVERFLOW SHALL DRAIN TO | | | STORM, NOT SANITARY WASTE. PLEASE REVISE. | | | | | | 7. PLANS SUBMITTED WITH REVISIONS TO THE BASE BUILDING | | | SHALL BE SUBMITTED AS REVISIONS UNDER THE BLD-COM | | | PERMIT NUMBER, NOT WITH THE FOUNTAIN APPLICATION. | | | PLEASE SUBMIT REVISIONS UNDER THE CORRECT PERMIT | | | NUMBER. (05091425). | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|