2007-07-13 15:22:38**** UNSAT ****
  
 1) NOTE: PLEASE SEE THE SUBMITTED DOCUMENTS REQUIRE THE
 CODES TO BE STATED ON PLANS. PLEASE SEE THE FOLLOWING
 ARE REQUIRED FOR ELECTRICAL AND OTHERS WILL BE REQUIRED
 FOR OTHER TRADES. PLEASE KNOW AS OF DECEMBER 8TH, 2006
 THE STATE ADOPTED THE 2006 REVISIONS TO THE 2004 FBC.
 PLEASE LIST THE FOLLOWING
 2004 FBC W/ 2006 REVISIONS.
 2005 NFPA-70
  
  
 2) NOTE: PLEASE SEE THE TITLE BLOCKS ARE STATING THE
 SOUTH FLORIDA BUILDING CODE WHICH HAS NOT BEEN IN
 EFFECT FOR SEVERAL YEARS. PLEASE SEE COMMENT ABOVE AND
 ADJUST TITLE BLOCKS.
 THIS COMMENT IS FOR ALL SHEETS AND FOR ALL TRADES
 WHETHER OR NOT COMMENT IS MADE BY OTHER TRADE
 REVIEWER(S).
 FBC 106.1.2
 ** COMMENT PREVIOUSLY MADE ON OTHER PROJECTS
  
 3) NOTE: PLEASE SEE THE MISSING LICENSE INFORMATION FOR
 THE FIRM. PLEASE SEE MISSING CERTIFICATE OF
 AUTHORIZATION NUMBER.
 FAC 61G15-23.002 AND FS 471.023.
 ** COMMENT PREVIOUSLY MADE ON OTHER PROJECTS.
  
 4) NOTE: PLEASE IDENTIFY WHICH PANEL IS THE NEW ONE
 BEING FED. THE BASE BUILDING REFERENCED PLANS ARE
 INDICATING NUMEROUS PANELS HOWEVER THE NEW SHEETS
 SHOULD INDICATE THE PANEL FEED ETC.
 215.5, 230, 240, 310.16 ETC
 FBC 106.1.2
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT ELECTRICAL PLANS AND DESIGN CHANGES.
  