| Plan Review Notes For Permit 07060834 |
| Permit Number |
07060834 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-08-28 12:09:38 | | | | | | | REVISION DENIED | | | | | | 1} HAND DRAWN CHANGES TO THE PLAN ARE NOT ACCEPTABLE | | | FOR RECORD RETENTION OR CLARITY IN THE FIELD. 106.1.3 | | | FBC AS AMENDED. | | | | | | 2} INDICATE A DISCONNECTING MEANS FOR THE WATER HEATER. | | | SEE 422.16 NEC FOR CORD AND PLUG RESTRICTIONS, AND | | | 422.31(B) FOR HARDWIRE REQUIREMENTS. THE WATER HEATER | | | MUST BE ADDED TO THE LOAD CALCULATIONS. THE ADDED | | | WATER HEATER REQUIRES PLUMBING REVISIONS. | | | | | | 3} THE EXHAUST FAN REVISION IN THE BATH ROOM MAY | | | REQUIRE A MECHANICAL REVISION. | | | | | | 4} THE PANEL IN THE KITCHEN (B) IS IN VIOLATION OF | | | 110.26 AS WAS NOTED IN THE PERMIT SET OF PLANS. | | | INDICATE HOW THIS WILL BE RESOLVED. | | | | | | THIS IS NOT A SUBMITTAL IT IS A REVISION AS THERE HAVE | | | BEEN SEVERAL CHANGES TO THE PERMITTED DRAWING. THE | | | DESIGNER IF RECORD NEEDS TO PRINT AND SIGN HIS NAME ON | | | BOTH SETS. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | [email protected] |
|