Plan Review Notes
Plan Review Notes For Permit 07060834
Permit Number 07060834
Review Stop E
Sequence Number 1
Notes
Date Text
2007-08-28 12:09:38 
  
 REVISION DENIED
  
 1} HAND DRAWN CHANGES TO THE PLAN ARE NOT ACCEPTABLE
 FOR RECORD RETENTION OR CLARITY IN THE FIELD. 106.1.3
 FBC AS AMENDED.
  
 2} INDICATE A DISCONNECTING MEANS FOR THE WATER HEATER.
 SEE 422.16 NEC FOR CORD AND PLUG RESTRICTIONS, AND
 422.31(B) FOR HARDWIRE REQUIREMENTS. THE WATER HEATER
 MUST BE ADDED TO THE LOAD CALCULATIONS. THE ADDED
 WATER HEATER REQUIRES PLUMBING REVISIONS.
  
 3} THE EXHAUST FAN REVISION IN THE BATH ROOM MAY
 REQUIRE A MECHANICAL REVISION.
  
 4} THE PANEL IN THE KITCHEN (B) IS IN VIOLATION OF
 110.26 AS WAS NOTED IN THE PERMIT SET OF PLANS.
 INDICATE HOW THIS WILL BE RESOLVED.
  
 THIS IS NOT A SUBMITTAL IT IS A REVISION AS THERE HAVE
 BEEN SEVERAL CHANGES TO THE PERMITTED DRAWING. THE
 DESIGNER IF RECORD NEEDS TO PRINT AND SIGN HIS NAME ON
 BOTH SETS.
  