| 2007-11-02 12:11:26 | |
| | ** DENIED 3RD REVIEW ** |
| | |
| | ** PLEASE SEE SOME COMMENTS FROM PREVIOUS REVIEWS |
| | INCLUDING NEW COMMENTS ARE STILL NEEDED TO BE |
| | ADDRESSED. |
| | |
| | |
| | 1) NOTE: PLEASE SEE 210.52B1, 210.11C1, 220.53 AS THE |
| | DINING ROOM RECEPTACLES SHALL BE ON ONE OR MORE OF THE |
| | SMALL APPLIANCE CIRCUITS. IF MORE THAN THE TWO MINIMUM |
| | THEN PLEASE SEE THE ADDITIONAL VA IS 1500 VA FOR EACH. |
| | PANEL AND LOAD ONLY SHOWS 1.0 KVA. |
| | |
| | |
| | 2) NOTE: PLEASE SEE THE PANEL SCHEDULE HAS NOW CHANGED |
| | THE AHU HEAT DOWN TO 5KW WHEN THE PREVIOUS HAD THE HEAT |
| | AS 10KW. THE PREVIOUS REVIEW GAVE A NOTICE TO 424.3B AS |
| | THE CIRCUIT WAS A SINGLE POLE 20AMP CIRCUIT. THERE WAS |
| | NO COMMENT ABOUT THE KW RATING TO BE CHANGED. PLEASE |
| | SEE THE LOAD CALCULATIONS STILL CONTAIN 10KW WHEN PANEL |
| | IS 5KW. |
| | PLEASE COORDINATE AND ADJUST. FBC 106.3.5.4, 106.1.2, |
| | NEC 310.16, 240.4 ETC |
| | ** PLEASE SEE THE OVER CURRENT PROTECTION AND CIRCUIT |
| | SIZE FOR THE 3-TON CONDENSING UNIT IS TOO HIGH. PLEASE |
| | KNOW THE MAXIMUM OVER CURRENT PROTECTION IS STATED IN |
| | THE NEC AND BY THE MANUFACTURE. |
| | 110.3, 90.7, 422.11E(3) |
| | |
| | 3) NOTE: PLEASE SEE PREVIOUS COMMENT WITH RESPECT TO |
| | THE OWNER BUILDER APPLYING FOR AN OWNER BUILDER PERMIT |
| | WHEN HOMESTEAD EXEMPTION IS LISTED ON MULTIPLE |
| | PROPERTIES. THIS WILL BE VERIFIED WITH THE BUILDING |
| | OFFICIAL AND LAW DEPARTMENT. CONTACT MAY BE MADE TO THE |
| | PROPERTY APPRAISER'S OFFICE TO VERIFY THE ALLOWANCE AS |
| | STATED IN FS 489. |
| | |
| | 4) NOTE: PLEASE SEE THE SMOKE ALARMS ARE NOT CIRCUITED |
| | SO THE VERIFICATION OF THE REQUIRED ARC FAULT |
| | PROTECTION PER 210.12. |
| | |
| | 5) NOTE: PLEASE SEE CODE AS LISTED FOR BATH CIRCUIT |
| | DOES NOT NEED TO BE ON PLANS. THIS IS SHOWN AS |
| | 210.11-2-3, HOWEVER THE CORRECT CODE IS 210.11C3. THIS |
| | WOULD HAVE BEEN REDLINED IF THIS WAS THE ONLY ITEM. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |