| 2007-07-16 08:30:39 | DENIED BY BUILDING |
| | |
| | 1) IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY, PLANS STAMPED BY THEM AND |
| | COPY OF RECEIPT SUBMITTED TO CITY OF |
| | WEST PALM BEACH BUILDING DEPARTMENT, |
| | BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| | |
| | 2) A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 3) SUBMIT A DRAINAGE PLAN SHOWING COMPLIANCE WITH FBC R |
| | 401.3. SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM |
| | SEWER CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION |
| | SO AS NOT TO CREATE A HAZARD. LOTS SHALL BE GRADED SO |
| | AS TO DRAIN SURFACE WATER AWAY FROM FOUNDATION WALLS. |
| | THE GRADE AWAY FROM FOUNDATION WALLS SHALL FALL A |
| | MINIMUM OF 6 INCHES WITHIN THE FIRST 10 FEET. |
| | |
| | 4) THE ENERGY CALCULATION FORMS ARE REQUIRED TO BE |
| | SIGNED BY THE OWNER/ AGENT PER FBC CHAPTER 13. |
| | |
| | 5) SHOW COMLIANCE WITH FBC R 309.1 AND 309.2 FOR |
| | OPENING PROTECTION (DOOR REQUIREMENTS) AND GARAGE |
| | SEPARATION (WALL REQUIREMENTS). |
| | |
| | 6) ON SHEET 3 THE EDITION OF SOME OF THE STANDARDS THAT |
| | WERE SPECIFIED ARE INCORRECT. IN ORDER TO COMPLY WITH |
| | THE EDITION OF THE STANDARDS REFERENCED IN THE 2004 |
| | FBC, PLEASE UPDATE TO ACI 530-02/ ASCE 7-02 AND TMS |
| | 402-02. |
| | |
| | 7) REVISE THE ROOF SHEATHING NAILING SCHEDULE ON SHEET |
| | 4. THE CORNERS OF HIP ROOFS ARE ALSO ZONE 3. SEE |
| | DIAGRAM FBC R301.2(8).R 803.2.3.1 REQUIRES 8D RING |
| | SHANK NAILS FOR ALL ROOF ZONES. |
| | |
| | 8) TWO COPIES OF ALL PRODUCT APPROVALS ARE REQUIRED. |
| | PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| | ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| | PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE STATE APPROVAL, BUT |
| | HAS A MIAMI-DADE NOA, THE NOA IS ACCEPTABLE BY ITSELF. |
| | |
| | 9) THE WINDOW SCHEDULE ON SHEET 2 HAS WINDOWS LISTED |
| | THAT ARE NOT USED IN THIS PROJECT. REVISE THE SCHEDULES |
| | TO ONLY LIST INFORMATION THAT PERTAINS TO THIS |
| | PROJECT. |
| | |
| | 10) SUBMIT PRODUCT APPROVALS FOR THE FOLLOWING: |
| | - SINGLE HUNG WINDOWS |
| | - ARCHED FIXED GLASS WINDOWS |
| | |
| | 11) THE PRODUCT APPROVAL FOR THE GAF SHINGLES HAVE BEEN |
| | REVISED. SUBMIT THE NEW STATE COVERSHEET AND THE NEW |
| | NOA # 05-1115.08. |
| | |
| | 12) THE PRODUCT APPROVAL SUBMITTED FOR THE MASONITE |
| | DOOR, FL 19 IS NO LONGER VALID. |
| | |
| | 13) SUBMIT PRODUCT APPROVALS FOR THE OVERHEAD GARAGE |
| | DOORS. |
| | |
| | 14) SUBMIT AN INSTALLATION SCHEDULE FOR THE STORM |
| | PANELS. SPECIFY THE CONNECTION/MOUNT TYPE, THE ANCHOR |
| | TYPES, THE ANCHOR SPACINGS, ETC.SEE ATTACHED. |
| | |
| | - ROBERT MCDOUGAL |