Plan Review Notes
Plan Review Notes For Permit 07060804
Permit Number 07060804
Review Stop E
Sequence Number 1
Notes
Date Text
2007-06-26 12:06:40*** UNSAT ***
  
 ** PLEASE KNOW THE PLANS ARE INCOMPLETE AT THIS TIME
 AND THERE ARE SEVERAL CODE RELATED ISSUES WHICH WILL BE
 REQUIRED SUBSTANTIAL CHANGES TO PLANS.
 ** PLEASE KNOW THERE ARE ITEMS WHICH CAN NOT YET BE
 REVIEWED FOR COMPLIANCE.
  
 1) NOTE: PLEASE SEE PLANS ARE MISSING THE FOLLOWING
 REQUIRED CODES TO BE STATED ON PLANS AND FOR DESIGN.
 PLEASE SEE THE FOLLOWING WHICH WAS ADOPTED AS OF
 DECEMBER 8TH, 2006.
 2004 FBC W/2006 REVISIONS.
 2005 NFPA-70
 2002 NFPA-72
  
 2) NOTE: PLEASE KNOW THE PLANS WILL BE ROUTED TO THE
 ADDRESSING REVIEWER AS THE PALM BEACH COUNTY PROPERTY
 APPRAISER OFFICE DOES NOT INDICATE AND ADDRESS, OUT
 SYSTEM SHOWS 715 59TH AND THE PLANS INDICATE 714 59TH.
  
 PLEASE KNOW ONCE THE ADDRESS HAS BEEN DECIDED AND
 CORRECTED, PLEASE REVISED TITLE BLOCKS OF PLANS
 ACCORDINGLY.
 FAC61G1-16.004
  
 3) NOTE: PLEASE SEE THE PLANS ARE INCOMPLETE AS NO
 ELECTRICAL RISER DIAGRAM WAS SUBMITTED.
 A) PLEASE SEE NO SERVICE ENTRANCE
 CONDUCTORS.215.5,240.4,310.16 ETC
 B) PLEASE SEE NO GROUNDING ELECTRODE SYSTEM WAS
 SUBMITTED. 250.50
 C) PLEASE SEE NO MAIN DISCONNECT WAS SHOWN FOR SERVICE.
 230.70, 230.71 ETC
 D) PLEASE INDICATE THE AIC RATINGS ON NEW RISER AS THE
 NOTED RATING ABOVE PANEL SCHEDULE MAY CHANGE ONCE THE
 RISER IS REVISED. 110.9
 E) PLEASE SEE LOCATIONS OF ALL SERVICE EQUIPMENT WERE
 SHOWN ON PLANS. 110.26, 240.24 ETC
  
 4) NOTE: PLEASE SEE THE RECEPTACLES ON KITCHEN COUNTER
 SPACE NEED TO MEET 210.52C1-5 AND 210.8A6.
  
 5) NOTE: PLEASE SEE MISSING GFI RECEPTACLE PER 210.52E,
 210.8A
  
 6) NOTE: PLEASE SEE MISSING THE RECEPTACLE FOR THE
 DISHWASHER AS THE PLANS ONLY APPEAR TO SHOW A COUNTER
 SPACE RECEPTACLE AND THE PANEL SCHEDULE DOES SHOW AS
 DISHWASHER CIRCUIT.
  
 7) NOTE: PLEASE SEE 210.52B1, 210.11C1 AND 220.53 AS
 THE LOADS FOR ALL SMALL APPLIANCE AND DINING ROOM
 CIRCUITS SHALL BE FIGURED INTO THE LOAD CALCULATIONS.
 PLEASE SEE THE FOLLOWING COMMENT.
  
 8) NOTE: PLEASE SEE THERE ARE NUMEROUS DEDICATED
 CIRCUITS ON PANEL SCHEDULE WHICH ARE NOT IN LOAD
 CALCULATIONS. PLEASE SEE THERE ARE OTHER ITEMS WHICH DO
 NOT MATCH.
 A) PLEASE SEE THE PANEL SCHEDULE SHOWS ONE WATER
 HEATER, YET THE LOAD CALCULATIONS INDICATES 2@450WATTS,
 YET THE TOTAL LOAD IS 9KW?
 B) PLEASE SEE THE PANEL SCHEDULE SHOW 2-AHU SYSTEMS AND
 ONLY ONE CU. IN EITHER CASE PLEASE SEE THE PANEL
 SCHEDULE SHOWS TWO 10KW UNITS AND LOAD CALCULATIONS
 ONLY INDICATE ONE 7.5KW AND 1-10KW?
 PLEASE SEE COMMENT WITH RESPECT TO PLANS.
 C) PLEASE SEE FRIG, APPLIANCES, DISHWASHER ETC. PLEASE
 SEE ALL OF NEC 220 AS THERE ARE TOO MANY MISSING AND
 COORDINATION NEEDS TO BE ADDRESSED.
 FBC 106.1.2, 106.3.5.4
  
 9) NOTE: PLEASE SEE 210.11C2, 220.53 AS THE LOADS FOR
 WASHER AND LAUNDRY SHALL BE BASED ON THE MINIMUM PER
 CODE AT 1500VA.
  
 10) NOTE: PLEASE SEE THE CLOSET LIGHT NEEDS TO MEET
 410.8
  
 11) NOTE: PLEASE SEE A PLAN INDICATES THE ELECTRICAL
 PANEL LOCATED WHERE IS DOES NOT MEET 110.26, 240.24,
 408.7.
 THIS LOCATION ON PLANS IS NOT PERMITTED.
  
 12) NOTE: PLEASE SEE THE REFRIGERATOR RECEPTACLE IS
 BEING SHOWN AS A 220V RECEPTACLE??
 FBC 106.1.2, 210.4?
  
 13) NOTE: PLEASE SEE THE PLANS NEEDS TO SHOW ALL
 LOCATION AND IDENTIFY THE LOCATIONS OF THE AHU AND
 WATER HEATER.
 PLEASE SEE MISSING DISCONNECTS PER 440.11 AND 422.31
  
 14) NOTE: PLEASE SEE 422.13 UNDER THE 2005 NEC AS THE
 WATER HEATER NEEDS TO BE SHOWN AT 125%.
  
 15) NOTE: PLEASE SEE THE PLAN INDICATES BOTH A 220V
 RECEPTACLE AND A DISCONNECT FOR THE CU??
 THE HARDWIRED DISCONNECT IS REQUIRED.
  
 16) NOTE: PLEASE SEE THE PANEL SCHEDULE SHALL BE
 SPECIFIC FOR ALL CIRCUIT NUMBERS AND DESIGNATIONS ON
 EACH CIRCUIT SHALL BE SPECIFIC TO ALL ROOMS AND AREAS
 IN WHICH THEY FEED.
 LISTING THE NUMERICAL DESIGNATIONS AS SHOWN IS NOT
 ACCEPTABLE AND LISTING THE GENERAL LTS AND RECEPTS MAY
 NOT BE USED. PLEASE SEE THE FOLLOWING TEXT WHICH HAS
 BEEN EXTRACTED DIRECTLY FROM THE NEC IN 408.4. *SECTION
 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE THAT THE
 IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A
 PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE
 THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED.
 CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED
 AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE
 BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN,
 DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE
 CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT
 ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS
 ``KITCHEN WALL RECEPTACLES,'' ``DINING ROOM FLOOR
 RECEPTACLE,'' OR ``KITCHEN COUNTERTOP RECEPTACLES LEFT
 OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE
 ENTRIES WITH ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT
 PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS
 SECTION.*
 408.4, 310.16, 240.4 ETC
 FBC 106.3.5.4
  
 17) NOTE: PLEASE LIST THE REQUIRED ARC FAULT PROTECTED
 CIRCUITS ON PANEL SCHEDULE. THE GENERAL NOTE IS NOT
 ACCEPTABLE. SEE NOTE ABOVE.#16. IDENTIFY EACH.
  
 18) NOTE: PLEASE INDICATE THE TYPE OF RECESSED LIGHTS
 PER FBC 13-606.1.ABC.1.2.4
  
 19) NOTE: PLEASE SEE THE KITCHEN LIGHTING NEED SOT BE
 ON A 3-WAY SWITCH PER 210.70 AND LS 101 7.8 FOR EGRESS
 INTO THE KITCHEN AREA.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT ELECTRICAL PLANS AND DESIGN CHANGES.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  