| Plan Review Notes For Permit 07060790 |
| Permit Number |
07060790 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2007-07-31 14:35:20 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* | | | CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC | | | FLORIDA ADMINISTRATIVE CODE | | | FSFLORIDA STATUTE | | | | | | 1.)SEE OPENING 5.FBC R TABLE 301.2(2) AND 301.2(3) | | | REQUIRE A DESIGN PRESSURE OF -38.2 FOR 10SF, MULTIPLIED | | | BY 1.29 FOR MRH OF 20', EXPOSURE C, FOR A DESIGN | | | PRESSURE OF -49.28.YOU ARE DESIGNING TO -45PSF.YOUR | | | PRODUCT APPROVAL REQUIRES USE OF THE -77PSF ROW FOR | | | PRESSURES OVER -47.2, SO THE ANCHOR SPACING OF 6"/6" IS | | | NOT COMPLIANT FOR THIS OPENING. | | | | | | CHECK ALL OPENINGS.THIS COMMENT APPLIES TO OTHER | | | OPENINGS.YOU MUST DESIGN USING EITHER FBC TABLE | | | R301.2.1(2) AND (3), FBC R 301, OR WITH AN ARCHITECT OR | | | ENGINEER USING ASCE7-02. | | | |
|