| Plan Review Notes For Permit 07060773 |
| Permit Number |
07060773 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-07-09 08:27:35 | DENIED; | | | 1. FLOOR DRAIN SHOULD BE A WASTE RECEPTOR WITH AN | | | INTERIOR STRAINER. FBC-2004 PLUMBING SECTIONS 802.2 AND | | | 802.3. | | | 2. WATER HAMMER ARRESTOR IS REQUIRED ON HOT WATER TO | | | THE DISHWASHER. SECTION 604.9 | | | 3. BREAK SINK TO MEET ACCESSIBILITY CODE SECTIONS | | | 11-4.24.1 THRU 11-4.23.7 | | | A) 11-4.24.3 THE FRONT OF CABINET TO BE | | | OPEN FOR KNEE CLEARANCE OF 19" UNDER SINK. ALSO THE | | | GARBAGE DISPOSAL MUST BE OFF SET OR DELETED. | | | B) 11-4.24.4 DEPTH OF SINK TO BE A MAXIMUM | | | OF 6 1/2" DEEP. ( SHOW ON PLANS) | | | C) EXPOSED PIPES TO BE INSULATED. | | | PLUMBING PLAN REVIEW BY: | | | JOHN LEECH | | | 805-6695 |
|