| 2007-07-25 10:55:59 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| | CODE |
| | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* |
| | CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC |
| | FLORIDA ADMINISTRATIVE CODE |
| | FSFLORIDA STATUTE |
| | |
| | 1.)PRODUCT APPROVALS ARE TO BE APPROVED BY DESIGNER |
| | OF RECORD (SHOP DRAWING REVIEW STAMP OR LETTER), |
| | FBC*106.3.3. |
| | |
| | 2.)FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED |
| | IN ADDITION TO THE NOA SUBMITTED, FAC9B72. |
| | WWW.FLORIDABUILDING.ORG |
| | |
| | 3.)GOVERNING CODE IS TO INCLUDE 2005 AND 2006 |
| | AMENDMENTS. |
| | |
| | 4.)N/A |
| | |
| | 5.)FOR ALL OF THE FIRE RATED ASSEMBLIES, SHOW |
| | CALCULATED FIRE RESISTANCE OR TESTED ASSEMBLY FBC 7. |
| | |
| | 6.)IN THE BUILDING CODE SUMMARY ON A1, PLEASE PROVIDE |
| | THE TOTAL SQUARE FOOT AREA PER FLOOR, FBC TABLE 503. |
| | |
| | 7.)THE PLAN SHOWS THE EXTERIOR WALLS AND 2ND FLOOR |
| | CEILING AS RATED.PROVIDE A SITE PLAN AND SHOW |
| | COMPLIANCE WITH FBC TABLE 601, FBC TABLE 602, FBC TABLE |
| | 704.8.ARE THEY REQUIRED TO BE RATED WALLS OR ARE YOU |
| | EXCEEDING CODE COMPLIANCE?IT IS NOT CLEAR IF THE |
| | OPENINGS IN THE RATED WALLS ARE TO BE PROTECTED. |
| | |
| | 8.)ROOF FELT UNDERLAYMENT FASTENING IS SPECIFIED.IT |
| | IS NOT CLEAR WHERE THIS WILL BE USED.EITHER REMOVE OR |
| | SHOW LOCATION OF WORK AND PROVIDE PRODUCT APPROVAL FOR |
| | THE ROOF ON A2 AND CONFIRM COMPLIANCE WITH FASTENING |
| | REQUIRED BY THE PRODUCT APPROVAL. |
| | |
| | 9.)SHOW ALL REQUIRED FIRE RESISTANCE RATED WALLS ON |
| | THE FLOOR PLAN. |
| | |
| | 10.)PROVIDE INFORMATION IN REGARDS TO THE TENANT |
| | SEPARATION WALL.SHOW REQUIRED FIRE RESISTANCE AND HOW |
| | THAT IS ACCOMPLISHED.NOTE THAT EXTERIOR WALLS ARE |
| | SHOWN AS FIRE RATED BUT THE INT BEARING WALL IS NOT, |
| | BUT IT APPEARS THAT THE BEARING WALL IS THE TENANT |
| | SEPARATION WALL AND IS REQUIRED TO HAVE A 1 HOUR RATING |
| | FBC708.1.AS SHOWN THE WALL DOES NOT MEET THE |
| | CONTINUITY REQUIREMENTS OF FBC708.4.SEE ALSO FBC EB |
| | 703.2. |
| | |
| | 11.)A1, THE ROOF IS A FLAT DECK WITH NO PARAPET WALL |
| | SHOWN; PROVIDE CALCULATIONS FOR THE CORNER PRESSURE OF |
| | -62.8. |
| | |
| | 12.)THE PLAN SHOWS THAT THE LANDING AND STAIRWAY ARE |
| | UNDER SEPARATE PERMIT.THIS IS IN CONFLICT WITH THE |
| | APPLICATION WHICH STATES THAT THE STAIRS AND LANDING |
| | ARE WITHIN THE SCOPE OF THIS PERMIT. |
| | |
| | 13.)EXTERIOR STAIRS TO COMPLY WITH ALL REQUIREMENTS |
| | OF FBC1022.SHOW FIRE RESISTANCE RATING FOR THE WALL |
| | AS WELL AS OPENINGS. |
| | |
| | 14.)SHOW THAT THE DOOR FOR THE SECOND FLOOR UNIT EXIT |
| | DOORS MEET WIDTH REQUREMENTS OF FBC1008.8.8 (MEASURE |
| | FROM EACH DOOR TO THE CORNER OF STAIR/GUARDRAIL). |
| | |
| | 15.)ONLY ONE HANDRAIL IS SHOWN.A HANDRAIL ON EACH |
| | SIDE IS REQUIRED FBC1009.11.SHOW HANDRAILS AS |
| | REQUIRED, WITH EXTENSIONS FBC1009.11.5. |
| | |
| | 16.)SHOW DIMENSIONS OF THE SLOPED HANDRAIL EXTENSION |
| | AT THE BOTTOM OF THE STAIR, FBC1009.11.5 (WEST |
| | ELEVATION). |
| | |
| | 17.)ROOF NAILING PATTERN DOES NOT COMPLY WITH FBC |
| | TABLE 2304.9.1 (31) FOR 10D NAILS. |
| | |
| | 18.)SEE ATTACHED POLICY IN REGARDS TO HURRICANE |
| | SHUTTERS, ITEM 13.SUBMIT AN INSTALLATION PLAN.USE |
| | OF REMOVABLE SHUTTERS ON COMMERCIAL BUILDINGS MUST BE |
| | APPROVED BY THE BUILDING OFFICIAL.THIS MAY BE DONE |
| | INDEPENDENTLY FROM THE PLAN REVIEW PROCESS AND A |
| | PRELIMINARY PLAN CAN BE SUBMITTED VIA EMAIL TO |
| | [email protected] DO NOT SUBMIT THIS PLAN WITH THE |
| | PERMIT APPLICATION RESUBMITTAL AS THIS SHOULD BE |
| | RESOLVED PRIOR TO RESUBMITTAL.FAILURE TO ADDRESS THIS |
| | COMMENT WILL RESULT IN DELAYS IN PERMITTING.PLEASE |
| | CONTACT ME IF YOU NEED FURTHER INFORMATION. |
| | |
| | 19.)STAIR TREAD TO BE 11IN MINIMUM, FBC1009.3. |
| | |
| | 20.)PROVIDE A HANDRAIL DETAIL FBC10 AND SPECIFY |
| | DESIGN STRENGTH FBC16.NOTE THAT THE STAIR AS DRAWN, |
| | WEST ELEVATION, DOES NOT MEET THE CONTINUITY |
| | REQUIREMENT FBC1009.11.4. |
| | |
| | 21.)THE GUARD IS TO MEET THE HEIGHT REQUIREMENT OF |
| | FBC1012.2, INCLUDING THE GUARD AT THE STAIRS.THE |
| | EXTERIOR STAIRS DOES NOT FALL UNDER THE EXCEPTIONS. |
| | ALSO PLEASE SEE FBC1009.11.1, EXCEPTION REGARDING STAIR |
| | RAIL HEIGHT. |
| | |
| | 22.)IT APPEARS THAT THIS IS S FOUR UNIT BUILDING, BUT |
| | THERE ARE ONLY TWO UNIT DESIGNATION NUMBERS (#1 AND #2, |
| | ON FIRST AND SECOND FLOORS). |
| | |
| | 23.)A2 STATES THAT FRAMING WILL BE IN ACCORDANCE WITH |
| | CURRENT NDS CODE.THIS IS NOT REFERENCED IN THE FBC, |
| | SEE CHAPTER 35.PLEASE CHECK ALL REFERENCES ON THE |
| | PLAN FOR ANY WHICH MAY BE IN CONFLICT WITH FBC. |
| | |
| | 24.)PROVIDE A DETAIL FOR PENETRATIONS THROUGH THE |
| | FIRE RATED WALLS AND FLOOR/CEILING ASSEMBLIES FBC7. |
| | |
| | 25.)ELEVATIONS CONFLICT AS TO TYPE OF DOOR TO BE |
| | INSTALLED.ONE SHOWS A GLAZED DOOR, ANOTHER SHOWS |
| | OPAQUE.PLANS SHOULD BE CLEAR AS TO WHAT IS PROPOSED, |
| | AND PRODUCT APPROVALS ARE TO BE SUBMITTED FOR ALL |
| | COMPONENTS AND CLADDING. |
| | |
| | 26.)THE DOOR PRODUCT APPROVALS ARE FOR INSWING DOUBLE |
| | OPAQUE DOORS.NONE ARE SHOWN ON THE PLAN. |
| | |
| | 27.)SEE ATTACHED INSTALLATION SCHEDULE.EITHER |
| | COMPLETE THIS FORM OR PROVIDE ALL REQUIRED INFORMATION |
| | IN ANOTHER FORMAT FOR THE HURRICANE SHUTTERS.THIS |
| | SHOULD CORRELATE WITH A KEY PLAN SHOWING SHUTTER |
| | LOCATIONS.THIS APPLIES TO FIRST FLOOR WINDOWS ONLY. |
| | SECOND FLOOR WINDOWS ARE REQUIRED TO BE IMPACT RATED |
| | |
| | 28.)EXTERIOR CHANGES TO THE PLAN WILL REQUIRE |
| | HISTORIC REVIEW PRIOR TO RESUBMITTAL. |
| | |
| | 29.)PROVIDE SLIDING GLASS DOOR PRODUCT APPROVALS. |
| | |
| | 30.)DOOR SWING CONFLICTS ON A1 AND A4.IF YOU ARE |
| | INSTALLING INSWING DOORS, PROVIDE PRODUCT APPROVALS. |
| | |
| | 31,)SHOW ALL SAFETY GLAZING REQUIREMENTS ON THE FLOOR |
| | PLAN OR WINDOW SCHEDULE, FBC2406. |
| | |
| | 32.)THE ISSUES REGARDING THE 4X FEE FOR THIS PROPERTY |
| | ARE TO BE ADDRESSED PRIOR TO PERMIT ISSUANCE. |
| | |
| | 33.)WHEN RESUBMITTING, PROVIDE A RESPONSE LETTER |
| | INDICATING HOW EACH COMMENT WAS ADDRESSED. |