Plan Review Notes
Plan Review Notes For Permit 07060770
Permit Number 07060770
Review Stop B
Sequence Number 4
Notes
Date Text
2007-09-10 15:28:16****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC
 FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.)PREVIOUS LIST NOTED THE FACTOR REQUIREMENT FOR
 EDGE DISTANCE LESS THAN 3 1/2".SEE OPENING 2.A 2"
 EDGE DISTANCE REQUIRES A .5 FACTOR; ANCHOR SPACING TOP
 AND BOTTOM SHOULD BE 4.5.CHECK ALL OPENINGS.
  
 2.)ALSO SEE PREVIOUS LIST IN REGARDS TO OPENING 8.
 2" EDGE DISTANCE CANNOT BE USED AS 5.5 SPACING WITH A
 FACTOR OF .5 EQUALS 2.75", MINIMUM IS 3" SPACING.
  