2007-08-29 15:40:03****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC
 FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 FROM PREVIOUS LIST:
  
 1.)SEE OPENING 8.WALL MOUNT INTO CBS, .5 FACTOR FOR
 2" EDGE DISTANCE REQUIRES 2.75 SPACING WHICH IS NOT
 ALLOWED (3" MINIMUM).YOU HAVE SPECIFIED SPACING OF
 6.2PLEASE REVISE.CHECK ALL OPENINGS.
  
 THE SAME INSTALLATION SCHEDULE WAS SUBMITTED (I HAD
 CIRCLED THE ANCHORING FOR OPENING 8, 6.2).PLEASE
 REVISE AND MARK VOID ON OLD SHEETS.
  
  