Plan Review Notes
Plan Review Notes For Permit 07060770
Permit Number 07060770
Review Stop B
Sequence Number 1
Notes
Date Text
2007-07-06 16:34:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.)PLEASE EXPLAIN WHY THE SPAN FOR OPENING 1 IS 145"
 FOR A 103" OPENING.REVISE ALL SPANS AS NECESSARY.
  
 2.)SEE SHEET 14A.A .86 FACTOR REQUIRED FOR 3" EDGE
 DISTANCE.
  
 3.)4 1/2" REQUIRED FOR THE FLOOR MOUNT WITHOUT THE
 .86 FACTOR.CHECK ALL OPENINGS.
  
 4.)OPENING 1 STATES FLOOR/CEILING, ANCHORING IS
 TOP/BOTTOM, SHOULD THIS BE CEILING/FLOOR?
  
 5.)OPENING 3, BOTTOM IS WALL, 6.2".SEE SHEET 14A,
 CBS REQUIRES 5 1/2" WITHOUT THE .86 FACTOR.PLEASE
 REVISE.CHECK ALL OPENINGS AS THERE MAY BE OTHER
 ERRORS.