| 2007-10-20 12:28:14 | ** DENIED 2ND REVIEW ** |
| | |
| | *** PLEASE SEE SOME COMMENTS FROM PREVIOUS REVIEW ARE |
| | STILL IN NEED OF ADDRESSING. |
| | PLEASE SEE NEW NOTE ALSO. |
| | |
| | 1) NOTE: PLEASE SEE AS MENTION BY THE BASE BUILDING |
| | DESIGNER OF RECORD. THE NOTE ON E2.1 *SHEET NOTE #2* |
| | DOES MENTION THAT ALL RECEPTACLES ARE TO BE WIRED TO |
| | PANEL HL, YET ALL CIRCUITS FOR RECEPTACLES ON PLANS |
| | CALL FOR PANEL HL2. THIS IS AN ITEM WHICH COULD BE |
| | REDLINED HOWEVER PLANS ARE COMING BACK FOR COMMENTS |
| | FROM OTHER NOTES, PLEASE ADDRESS AT THIS TIME. |
| | |
| | 2) NOTE: PLEASE SEE PREVIOUS NOTE MENTIONED TO |
| | COORDINATE AND SEE ADDRESSING REVIEWER FOR SUITE/UNIT |
| | NUMBER. IT WAS MENTIONED TO PLEASE INDICATE ON |
| | APPLICATION ONCE THIS WAS DETERMINED BASED ON THE |
| | ADDRESSING REVIEWER HOWEVER APPLICATION STILL DOES NOT |
| | SHOW THIS. |
| | THIS HAS NOT BEEN ADJUSTED IN OUR SYSTEM AND THIS |
| | INFORMATION WAS E-MAILED TO THE ADDRESSING REVIEW FOR |
| | CORRECTION AND COORDINATION. |
| | THE TITLE BLOCKS WERE CHANGED TO SHOW SUITE/UNIT #110. |
| | |
| | 3) NOTE: PLEASE SEE AS MENTIONED ON THE PREVIOUS REVIEW |
| | AND AS GONE OVER WITH BOTH DESIGNERS FROM ICE |
| | ENGINEERING THESE PLANS ARE BEING REQUIRED TO CONTAIN |
| | STAMPS FOR *SHOP DRAWING* REVIEW BY THE DESIGNERS OF |
| | RECORD FOR THE BASE BUILDING. PLEASE KNOW THIS IS NOT |
| | FOR THESE ENGINEERS TO SIGN AND SEAL PLANS, IT IS FOR |
| | SHOP DRAWING REVIEW STAMP WHICH WILL BE SIGNED AND |
| | ACKNOWLEDGES THE PLANS AND CHANGES WHICH WILL AFFECT |
| | THE BASE BUILDING ELECTRICAL AND OTHER SYSTEMS. THIS |
| | BUILDING IS STILL UNDER THE RESPONSIBILITY OF THE BASE |
| | BUILDING DESIGN TEAM UNTIL SUCH TIME A CERTIFICATE OF |
| | OCCUPANCY (CO) IS ISSUED. THIS INCLUDES THE |
| | ARCHITECTURAL AND ENGINEERING FIRMS. |
| | FS 471/481, FAC 61G1-16, 61G15-23 |
| | |
| | ** THIS IS REQUIRED FOR ALL TRADES AND ALL REVIEWS |
| | WHETHER OR NOT COMMENT IS MADE BY OTHER TRADES. THIS |
| | WAS CLEARLY STATED ON THE PREVIOUS REVIEW. |
| | THIS WAS CONFIRMED WITH ASSISTANT BUILDING OFFICIAL MR. |
| | ROBERT BROWN. |
| | |
| | ** PLEASE BE SURE COORDINATION IS MADE WITH THE BASE |
| | BUILDING DESIGN TEAM. |
| | |
| | 4) NOTE: PLEASE SEE PANEL HL ON PLANS AND PANEL |
| | SCHEDULES IS STILL BEING SHOWN AS CONTAINING NO MAIN |
| | CIRCUIT BREAKER. THIS IS SHOWN AS MAIN LUG ONLY (MLO) |
| | WHEN A MAIN IS REQUIRED ON THE SECONDARY SIDE OF THE |
| | TRANSFORMER AS REQUIRED PER 408.36, 240.21, 240.4, |
| | 310.16 ETC. |
| | PLEASE SEE THE RESPONSE LETTER MENTIONS THIS WAS |
| | ADDRESSED HOWEVER BASED ON PLANS SUBMITTED THIS REMAINS |
| | THE SAME. |
| | ** BASE BUILDING PLANS DO CONTAIN A MCB ON THE |
| | SECONDARY SIDE OF ALL TRANSFORMERS. PLEASE COORDINATE |
| | WITH BASE BUILDING DESIGN TEAM AND MINIMUM CODE |
| | REQUIREMENTS. |
| | |
| | |
| | 5) NOTE: PLEASE PROVIDE CALCULATIONS/FIGURES ON HOW THE |
| | LPD WAS DERIVED. |
| | BASED ON SOME CALCULATIONS AND FIGURES DONE BY THIS |
| | OFFICE THERE IS SOME DIFFERENCES. |
| | PLEASE PROVIDE FRO EXAMPLE, SQ FT ON AREAS BASED ON |
| | SPACE BY SPACE WHICH WAS SHOWN. |
| | PLEASE SEE 13-415.2. |
| | |
| | 6) NOTE: PLEASE SEE PREVIOUS NOTE WITH RESPECT TO FBC |
| | 11-4.28.1, .2 AND .3(4) FOR MINIMUM LEVELS FOR FIRE |
| | ALARMS DEVICES TO BE STATED. PLEASE SEE THE LOCATIONS |
| | APPEAR TO MEET ADA REQUIREMENTS, HOWEVER MINIMUM LEVELS |
| | NEED TO BE STATED. PLEASE SEE ONLY TWO OF THE DEVICES |
| | ON THE NEW FA SHEET CONTAIN THE MINIMUM LEVELS NEEDED. |
| | |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |