| Plan Review Notes For Permit 07060745 |
| Permit Number |
07060745 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-07-03 11:32:17 | ***DENIED*** | | | | | | 1) PLEASE ADVISE IF EXIT DOOR THAT IS PART OF THE ONE | | | (1) HOUR WALL IS RATED. | | | | | | 2) IN ADDITION TO THE FIRE SPRINKLER REMODEL, SEPARATE | | | SHOP DRAWINGS AND PERMIT IS REQUIRED FOR FIRE ALARM | | | REMODEL. | | | | | | 3) HANDRAILS ARE REQUIRED FOR BOTH SIDES OF RAMP WHERE | | | HANDRAILS ARE REQUIRED. | | | | | | 4) NEW FIRE/SMOKE DAMPERS TO BE TESTED FOR CLOSURE IN | | | ACCORDANCE WITH UL 555 STANDARDS PRIOR TO FINAL | | | INSPECTION. | | | | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 804-4756 |
|