| 2007-06-29 17:49:40 | *** UNSAT *** |
| | |
| | *** PLEASE NOTE: AS THERE IS INFORMATION NOT YET |
| | SUBMITTED FOR REVIEW, THERE MAY VERY WELL BE NEW |
| | COMMENTS ON THE NEXT REVIEW AS THESE ITEMS CAN NOT BE |
| | REVIEWED AT THIS TIME. |
| | |
| | |
| | 1) NOTE: PLEASE SEE THE SUBMITTED DOCUMENTS REQUIRE THE |
| | CODES TO BE STATED ON PLANS. THIS WAS DONE ON |
| | ARCHITECTURAL SHEETS HOWEVER THE ELECTRICAL SHEETS ARE |
| | BLANK AT THIS LOCATION. |
| | PLEASE SEE THE FOLLOWING ARE REQUIRED FOR ELECTRICAL |
| | AND OTHERS WILL BE REQUIRED FOR OTHER TRADES. PLEASE |
| | KNOW AS OF DECEMBER 8TH, 2006 THE STATE ADOPTED THE |
| | 2006 REVISIONS TO THE 2004 FBC AND THE 2005 NFPA-70. |
| | PLEASE LIST THE FOLLOWING |
| | 2004 FBC W/ 2006 REVISIONS. |
| | 2005 NFPA-70 |
| | 2003 NFPA-101 |
| | 2002 NFPA-72 |
| | |
| | 2) NOTE: PLEASE SEE ALL MEP SHEETS IN ALL SETS ARE |
| | MISSING THE REQUIRED TITLE BLOCKS AND INFORMATION AS |
| | REQUIRED UNDER THE FLORIDA ADMINISTRATIVE CODE |
| | 61G15-23.002. |
| | PLEASE SEE MISSING INFORMATION IS ALSO REQUIRED UNDER |
| | FLORIDA STATUTES 471.023. |
| | ** THIS IS REQUIRED ON ALL MEP PLANS WHETHER OR NOT |
| | COMMENT IS MADE BY OTHER TRADE REVIEWER(S). |
| | |
| | 3) NOTE: PLEASE KNOW THAT PERMIT APPLICATION WAS |
| | SUBMITTED WITHOUT ANY SUITE/UNIT/SPACE #. PLEASE KNOW |
| | THAT A COPY OF THE PERMIT APPLICATION HAS BEEN |
| | FORWARDED TO THE ADDRESSING REVIEWER. ONCE THE |
| | SUITE/UNIT/SPACE NUMBER HAS BEEN DETERMINED PLEASE BE |
| | SURE THIS INFORMATION IS PLACED ON PLANS/TITLE BLOCKS. |
| | FAC 61G15-23.002, 61G1-16.004 |
| | |
| | 4) NOTE: PLEASE KNOW PLANS ARE BEING REVISED WHILE |
| | THERE IS STILL AN ACTIVE PERMIT FOR THE SHELL BUILDING. |
| | THE BASE SHELL BUILDING IS OF A DIFFERENT MEP DESIGN |
| | PROFESSIONAL AND ANY AND ALL CHANGES AND REVISIONS MADE |
| | TO BUILDING BY THE BUILD OUT DESIGNS AND WORK SHALL BE |
| | REVIEWED BY THE BASE BUILDING ENGINEER OF RECORD. |
| | (EXAMPLE: AS SHOP DRAWINGS) |
| | *** IMPORTANT** |
| | PLEASEALSO KNOW AS THERE ARE MANY ITEMS WHICH NOW |
| | AFFECT THE BASE BUILDING PLANS, COORDINATION OFNOW |
| | KNOWN LOADS FOR REVISED LOAD CALCULATIONS, KNOWN |
| | CHANGES FOR ENERGY CALCULATIONS, RISER INFORMATION, |
| | PANEL SCHEDULES ETC WILL ALL NEED TO BE GIVEN TO THE |
| | BASE BUILDING ENGINEER OF RECORD TO REVISED THE BASE |
| | BUILDING PLANS AND ENERGY CALCULATIONS. |
| | THERE ARE ITEMS WHICH WILL NOW AFFECT THIS. |
| | FBC 106.1.2, 106.3.5.1.2, |
| | NEC 408.4, 215.5, 230, 220, 240, 310 ETC. |
| | FBC CHAPTER 13, 13-415.1.AB.1.1, 13-415.2 ETC |
| | |
| | 5) NOTE: PLEASE SEE THE PANELS AS SHOWN ON PLANS ARE |
| | NOT ALL SHOWN ON THE SHEETS WHERE THE PANEL SCHEDULES |
| | ARE LOCATED. PLEASE CLARIFY THE MCB ON THE LOAD SIDE OF |
| | THE TRANSFORMER AS ON BASE BUILDING PLANS. |
| | 240.21, 408.36, 240.4, 310.16 ETC. |
| | FBC 106.1.2 FOR COORDINATION OF PLANS. |
| | |
| | 6) NOTE: PLEASE COMPLETE AND INDICATE ALL CIRCUITING ON |
| | PLANS WITH PANEL SCHEDULES. |
| | PLEASE SEE FOR EXAMPLE SOME OF THE EXIT LIGHTS WHICH |
| | ARE NOTED TO BE CIRCUITED TO THE LOCAL LIGHTING CIRCUIT |
| | DO NOT ACTUALLY SHOW THIS. THIS IS SHOWN FOR EMERGENCY |
| | LIGHTS AS REQUIRED PER 700.12F BUT NOT FOR ALL EXIT |
| | LIGHTS. |
| | PLEASE COMPLETE. |
| | FBC 106.1.2, 106.3.5.1.2. |
| | NEC 408.4. |
| | |
| | 7)NOTE: PLEASE SUBMIT PLANS FOR LIGHTING WHICH SHOWS |
| | COMPLETED INFORMATION FOR CHAPTER 13 CODE COMPLIANCE. |
| | PLEASE SEE SOME OF THE DEVICES ON PLANS INDICATE A NOTE |
| | * TO BE CHOSEN BY MANUFACTURES RECOMMENDATION*. THIS IS |
| | TO BE CHOSEN, DESIGNED, AND SHOWN AT THIS POINT. |
| | DESIGNS FOR CODE COMPLIANCE ARE NOT LEFT TO THE |
| | MANUFACTURE. |
| | PLEASE STATE DEVICE TYPES. |
| | PLEAS INDICATE MAXIMUM TIMES ON DEVICES CHOSEN. PLEASE |
| | SEE AREAS WHICH CONTAIN FLOOR TO CEILING HEIGHT |
| | PARTITIONS AND ALSO ANY WALLS THAT EXCEED 80%.(EXAMPLE, |
| | PLEASE SEE THE BATHROOMS WHICH INDICATE THE ADA STALLS |
| | WHICH APPEAR TO HAVE WALLS AND THE DEVICES AS SHOWN MAY |
| | NOT PROVIDE COVERAGE INTO THESE TWO AREAS. LIGHTING |
| | WHICH TURNS OFF WHILE PERSONS ARE IN AREAS WHICH CREATE |
| | A SAFETY ISSUE SHOULD BE ADDRESSED. |
| | PLEASE PROVIDE REVISED ENERGY CALCULATIONS AND LIGHTING |
| | POWER DENSITIES AS REQUIRED. PLANS STATE THE CODE, |
| | WHICH IS NOT ACCEPTABLE IN LIEU OF REQUIRED DESIGNS FOR |
| | MINIMUM CODE COMPLIANCE. |
| | PLEASE SEE THE FOLLOWING SECTIONS AT A MINIMUM. |
| | 13-415.1.ABC.1.1, .1.2 AND .1.3. |
| | 13-415.1.AB.1.1, 13-415.2. |
| | ETC. |
| | |
| | 8) NOTE: PLEASE SEE FBC 11-4.28.1, .2 AND .3(4) FOR |
| | MINIMUM LEVELS FOR FIRE ALARMS DEVICES TO BE STATED. |
| | PLEASE SEE THE LOCATIONS APPEAR TO MEET ADA |
| | REQUIREMENTS, HOWEVER MINIMUM LEVELS NEED TO BE |
| | STATED. |
| | IT IS KNOWN THAT THE FIRE ALARM SCOPE IS UNDER A |
| | SEPARATE PERMIT HOWEVER THE BASE PLANS ARE REQUIRED TO |
| | HAVE THE ADA COMPLIANCE SHOWN. |
| | ** PLEASE BE AWARE OF ANY CHANGES FROM BASE BUILDING |
| | AND BUILD OUT WHICH WILL NEED TO BE COORDINATED. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |